4 Application of VS 3015 C
The pack controller includes the following functions for the refrigeration compressor pack and condenser:
•
Control functions
•
Regulation functions
•
Monitoring functions
•
Fault signals
•
Archiving of messages and operating data
These functions include the following:
Low-pressure control / compressor control
•
as step controller
•
as combined control
Medium pressure regulation
High pressure regulation
Compressor control (step controller) for one-circuit systems with max.
•
6
*1
compressors with 2 capacity stages each or
•
4
*1
compressors with 3 capacity stages each or
•
12
*2
individual compressors without capacity regulation
•
*1 When using speed-controlled compressors with base load rotation or a spray system, the maximum
number of compressors is reduced by one compressor.
•
*2 When using speed-controlled compressors with base load rotation, the maximum number of
compressors is reduced by one compressor and reduced by two compressors when using a spray
system.
*1: When using speed-controlled compressors with base load rotation or a spray system, the maximum
number of compressors is reduced by one compressor.
*2: When using speed-controlled compressors with base load rotation, the maximum number of compressors is
reduced by one compressor and reduced by two compressors when using a spray system.
Fan control for one-circuit systems with max.
•
12
*3
fans
•
6 fans with separate star-delta switching of the fan motors (KKGG)
•
11 fans with common star-delta switching of the fan motors (KKGG)
*3: A maximum of 11 fans is possible for the "combined control" types of control.
Base load rotation
•
Compressors
•
Fans
Gas cooler regulation / fan control
•
as step controller
•
as speed controller
•
parallel combined control
•
stages combined control