14.01.2019
110/185
Terminal No.
Function
Base module SIOX 1 SIOX 2
-
50, 51
54, 55
58, 59
62, 63
-
Oil differential pressure / HP switch for compressor 5 *
Oil differential pressure / HP switch for compressor 6 *
Oil differential pressure / HP switch for compressor 7 *
Oil differential pressure / HP switch for compressor 8 *
-
-
50, 51
54, 55
58, 59
62, 63
Oil differential pressure / HP switch for compressor 9 *
Oil differential pressure / HP switch for compressor 10 *
Oil differential pressure / HP switch for compressor 11 *
Reserved
Digital inputs can be configured as:
•
oil differential pressure switch for compressor or
•
HP limiter for compressor or
•
oil differential pressure / HP switch for compressor
Terminal No.
Function
Base module SIOX 1 SIOX 2
56, 57
60, 61
64, 65
68, 69
-
-
Motor overload cutout, compressor 1
Motor overload cutout, compressor 2
Motor overload cutout, compressor 3
Motor overload cutout, compressor 4
-
52, 53
56, 57
60, 61
64, 65
-
Motor overload cutout, compressor 5
Motor overload cutout, compressor 6
Motor overload cutout, compressor 7
Motor overload cutout, compressor 8
-
-
52, 53
56, 57
60, 61
64, 65
Motor overload cut-out, compressor 9
Motor overload cut-out, compressor 10
Motor overload cut-out, compressor 11
Reserved
70, 71
-
-
Condenser fan 1 motor overload cutout *
or
Z2 compressor 1 FC fault
72, 73
-
-
Condenser fan 2 motor overload cut-out *
or
Z2 LP limiter
74, 75
-
-
Condenser fan 3 motor overload cut-out *
or
Z2 compressor 1 oil/HP fault
76, 77
-
-
Condenser fan 4 motor overload cut-out *
or
Z2 compressor 1 motor protection
-
66, 67
68, 69
70, 71
72, 73
-
Motor overload cutout, condenser fan 5 *
Motor overload cutout, condenser fan 6 *
Motor overload cutout, condenser fan 7 *
Motor overload cutout condenser fan 8 *
Summary of Contents for VS 3015 C