14.01.2019
174/185
SERVICE POS: XXXXX
Input
Default Dim.
AnalogOut4 X.XX V Voltage at the analogue output 4 (terminals 63, 64) 0.0..10.0 0.0
V
•
Menu 8-2 Compressor defaults ON/OFF
SERVICE POS: XXXXX
Input
Default Dim.
Leist.Stufe 1 XXX
Switching state of the respective compressor (stage) ON or OFF.
Only the actual number of compressors is displayed.
ON/OFF OFF
-
...
Leist.Stufe 12 XXX
ON/OFF OFF
-
VS 3015 C base module: 1 - max. 4 capacity stages
with first SIOX extension module 1 - max. 8 capacity stages
with second SIOX extension module 1 - max. 12 capacity stages
•
Menu 8-3 Condenser fan defaults ON/OFF
SERVICE POS: XXXXX
Input
Default Dim.
Lüfter 1 XXX
Switching state of the respective fan ON or OFF.
Only the actual number of condenser fans is displayed.
If ebmpapst fans are used for the gas cooler regulation, the switching states have
the following meanings:
ON:
ebmpapst fan is
100% controlled
OFF:
ebmpapst fan
is 0%
controlled (is off)
ON/OFF OFF
-
...
Lüfter 12 XXX
ON/OFF OFF
-
VS 3015 C base module: 1 - max. 4 fans
with first SIOX extension module 1 - max. 8 fans
with second SIOX extension module 1 – max. 12 fans
•
Menu 8-4 System defaults
SERVICE POS: XXXXX
Input
Default Dim.
Frei.Verb.Rel. XXX
Relay output 9 (terminals 1/2)
Enable consumer
ON or OFF
ON/OFF OFF
-
Verd.umsch. XXX
Relay output 10 (terminals 3/4)
Toggle FC compressor
ON or OFF ON/OFF OFF
-
• Menu 8-5 – Menu item is hidden