14.01.2019
164/185
•
Menu 3-4 Refrigerant monitoring
K.MITTEL Ü POS: XXXXX
Input Default.
Dim.
Intervall XXX m
Interval for refrigerant monitoring 2..60 30
Min.
Grenzwert XXX %
Limit value for alarm
20..99 50
%
•
Menu 3-5 External alarms
FREMDALARM POS: XXXXX
Input Default
Dim.
Verz Zeit XXX s
Time delay in seconds for
External Alarm
message
3..250 5
sec.
Alarm message:
XXXXXXXXXXXXXXXXXXX
Text that is displayed when external alarms occur:
Default text:
External Alarm
or
Speed Controller
Text
•
Menu 3-6 Base load
GRUNDLAST POS:
XXXXX
Input Defaul
t
Dim.
Zyklusz. Verd. XXX m
Cycle time for the compressor base load rotation
5..72
0
45
Min.
Umsch.Lüfter J/N
Activate base load rotation for condenser fans (only visible if the
"step controller"
type of HP control has been selected - screen 3-2-2-1-a)
Y/N N
-
B.Zeit-Ausgl. Y/N
Query for run time equalisation (only visible if
"Umsch.Lüfter"
is set to
Y)
Y/N N
-
Zyklusz. Lüft. XXX m
Cycle time for the condenser fans base load rotation (only visible if
"Umsch.Lüfter
is
set to
Y)
5..72
0
720
Min.
•
Menu 3 -7 Messages
Meldungen POS: XXXXX
Input
Default
Motortemp Verd X
Compressor motor overload cutout tripped
-, 0..99 2
Motorschutz LX
Fan motor protection (also alarms from ebmpapst fans) tripped
-, 0..99 2
Öl/HD-Störung X
Compressor oil differential pressure switch / HP monitor tripped
-, 0..99 2
Zyl. Temp. zu hoch X
Cylinder head temperature limit value exceeded
-, 0..99 2
HD-Begrenzer X
High pressure cutout tripped
-, 0..99 1
ND-Begrenzer X
Low pressure cutout tripped
-, 0..99 2
to zu tief X
Lower limit value t
0
undercut
-, 0..99 2