14.01.2019
152/185
with second SIOX extension module 1 - max. 12 capacity stages
•
Screen 3-2-1-4-d Variable time capacity stage OFF
Vari.Z.AUS POS: XXXXX
Input Default
Dim.
Vari.Z.AUS S1 XXX s
Only the available capacity stages are displayed.
3..250 20
sec.
Vari.Z.AUS S2 XXX s
3..250 40
sec.
Vari.Z.AUS S3 XXX s
3..250 60
sec.
Vari.Z.AUS S4 XXX s
3..250 80
sec.
Vari.Z.AUS S5 XXX s
3..250 100
sec.
Vari.Z.AUS S6 XXX s
3..250 120
sec.
...
Vari.Z.AUS S12 XXX s
3..250 120
sec.
VS 3015 C base module: 1 - max. 4 capacity stages
with first SIOX extension module 1 - max. 8 capacity stages
with second SIOX extension module 1 - max. 12 capacity stages
•
Menu 3-2-2 HP control
HD-REG POS: XXXXX
1 Regulation
Continue to menu 3-2-2-1
2 Setpoints
Continue to menu 3-2-2-2
•
Menu 3-2-2-1 Regulation
HD-REG
POS: XXXXX
Input Def
ault
Di
m.
Regelungsa
rt
→
Selection list of the HP control type
→
Screen
3-2-2-1-a
Switching
Order
→
To the submenu for defining the switching order.
→
Screen
3-2-2-1-b
EBM
Manual
ON
→
To the submenu for manual mode.
→
Screen
3-2-2-1-c
Min.
Drehzahl
XXX%
Min. condenser fan speed (only visible if the speed controller type of control has been selected -
screen 3-2-2-1-a)
0..50 0
%
Max.Drehza
hl T
Maximum speed that is output by the controller during the day
50..10
0
100 %
Max.Drehza
hl N
Maximum speed that is output by the controller during the night
30..10
0
100 %