6.4 Basic configuration of the controller
The lock-down must previously be deactivated on the higher level controller (system centre / store computer or
operator terminal) so that configuration settings can be made on the controller.
1. Cancelling entry block
A. BT 300 operator interface; for details, see chapter
Lock-down of the setpoint change
B. System centre via Login symbol; for details, see chapter
C. Store computer / operator terminal menu 8-3; for details, see chapter
Store computer CI 3x00 / operator
2. Opening main menu of the controller
A. The main menu of the controller is shown directly in the operator interface.
B. In the system centre, select the required controller in
Menu 4-2
and then tap the
Remote Control button
to
display the main menu of the controller.
C. In the store computer and operator terminal, a selection list of all CAN bus components is displayed in
Menu
5 Remote Control
. Select the controller with the corresponding CAN bus address (Kn,nnn = 1..99) to be
parametrised in the selection list using the cursor or direct input and recall by tapping the
ENTER
button so that
the main menu of the controller is displayed.
3. Basic configuration of the controller
- select refrigeration point (Menu 6-1)
In order to define the refrigeration point to be regulated by the case controller, various parameters can be
entered and checked:
6 Configuration - 1 Refrigeration point
KÜHLSTELLEPOS: XXX
Refr. Pt. Name: XXXXXX
Check refrigeration point name (can only be freely edited using system
centre)
Position: XXXXX
Check refrigeration point Item ID (can only be freely edited using system
centre)
Priority: X
Alarm priority 0..99 (observe notes in chapter 10.1 "Alarm signalling")
Verbund Nr.: X
Number of the compressor pack that supplies the refrigeration point (1 to 9,
important for multiple compressor packs)
Verbundsatz: XXX
Zone of the compressor pack that supplies the refrigeration point (Z1/Z2 only
for VS 3010 BS)
Temperaturzonen X
Division of the refrigeration point into 1 or 2 zones
Fühleranzahl XX
Number of sensors. The number of connected sensors is scanned after
leaving the parameter with the ENTER button.
The menus shown below only provide the overview; the display can be different for certain controller
types. Details are described in the chapter
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Page 244: ...Firmware V3 15 21 04 2021 244 401...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Page 372: ...Firmware V3 15 21 04 2021 372 401...