Firmware V3.15
21.04.2021
21/401
•
•
1.
2.
3.
4.
5.
6.
7.
•
5 Function of UA 400 / UA 410
5.1 Starting characteristics
The following are distinguished for any start-up of the controller:
First start
Restart
5.1.1 First start- reset controller to factory settings
The first start can be initiated using the following procedure:
Disconnect controller from the power supply for safety reasons (see also chapter
) make a note of the DIP switch S3 settings (e.g. OFF-ON-OFF-...).
Adjust settings at the DIP switch S3 (e.g. OFF-OFF-OFF-...).
Power on the controller again and wait approx. 1 minute while the controller starts up.
Disconnect controller from the power supply for safety reasons (see also chapter
).
Reset DIP switch S3 to the noted starting position.
Switch on controller again.
The settings of the controller have been reset to the factory settings.
5.1.2 Restart - restart of the controller
For a restart, the device is restarted with all configured parameters and the CAN bus address set on the rotary
switch. A restart can be initiated using the following procedure:
Disconnection and reconnection of the power supply
The parameters mentioned in this section are described in
. Changing the
default settings for these parameters will not normally be necessary. Parameters that cannot be
changed are referred to as fixed parameters in the following description.
Caution: data loss!
A first start causes all parameters to be reset to the factory settings!
A first start is also performed when a different controller version (e.g. UA 400 UA 410 D UA 400 E UA
410 L) is loaded on the controller via firmware update (see chapter
). A sensor
scan (Menu 6-1)
must
be performed during commissioning or after a first start! The sensor scan is the
only possibility to define the sensors to be monitored; see chapter
Necessary and optional sensors
.
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Page 244: ...Firmware V3 15 21 04 2021 244 401...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Page 372: ...Firmware V3 15 21 04 2021 372 401...