Firmware V3.15
21.04.2021
43/401
•
•
5.5.6
Master/slave mode – defrost synchronisation via wiring
All controller types versions >= V4.00
Requirements
External wiring on hardware side; for details, see chapter
Wiring of the master-slave function for defrost
.
Setting of the DIP switch S3, coding switch 4
must
be set to
ON
; for details, see chapter
controller type and master/slave mode
.
Function Description
The master/slave function is used for refrigerated cases when the operation of several evaporators, without
additional protective measures can result in the reciprocal icing of the evaporators (all controller types except
UA 131 DD).
This problem is prevented due to the defrost synchronisation in master/slave operation. All refrigerated cases
and case zones defrost simultaneously and then switch to cooling together. Multiple participating controllers are
synchronised via hardware wiring, see
Wiring of the master-slave function for defrost synchronization
In addition, in the case of
one
controller in two-zone operation, this can be used to force the joint return of both
zones to cooling following a defrost.
Damage to the installation and stock loss!
When using this function, it must be ensured that
incorrect parametrisation
does not result in simultaneous defrost and cooling of the synchronised
refrigeration points.
This function requires
additional external
wiring for multiple participating controllers. It must be
ensured for the wiring of master and slave case controllers that the power supply is only implemented
with
one phase
(e.g. only via L1).
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Page 244: ...Firmware V3 15 21 04 2021 244 401...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Page 372: ...Firmware V3 15 21 04 2021 372 401...