Firmware V3.15
21.04.2021
164/401
•
•
The value is selected in accordance with the entry. The check mark indicates the current setting.
FÜHLERTYP POS: XXXXX
Input
Default
L243
Temperature range -50..50 °C
K277
Temperature range -50..50 °C
5K3A1
Temperature range 0..100°C
Menu 6-3 Cooling
KÜHLUNG POS: XXXXX
Input
Default
min. Laufzeit XX K
Minimum run time of the cooling
0..15
2 m
min. Standzeit XX m
Minimum switch-off time of the cooling
0..15
2 m
Dauerl.überw. XX m
Time for the forced interruption of the cooling during
continuous operation
--, 0..15
0 m
Notbetrieb XX m
If necessary sensors for the regulation fail, the
solenoid valve is actuated with the opening degree in
[%]set here.
0..100
40%
Menu 6-4 - Language
SPRACHE POS: XXXXX
Input
Default
Deutsch D
English GB
Français F
Espagnol E
Finnish FIN
Türkce TR
Cesky CZ