Firmware V3.15
21.04.2021
208/401
•
DEFROST 1 POS: XXXXX
Entry
Default
DS-Wait time XXXm
Wait time for the defrost sequence
0..127
1 min
Menu 2-2-2 Zone 2
DEFROST 2 POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 5..20
8 °C
Wait Time xx m
Waiting time setpoint between cooling and
defrosting
0 .. 15
0 m
Drip Time x m
Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15
0 m