Firmware V3.15
21.04.2021
395/401
•
•
•
•
•
•
•
•
11.1.8 Alarm routes
A detected alarm state is transmitted by the controller by the following routes:
At the alarm relay (floating changeover contact 15/16/18)
A local BT 300 x Operator Interface connected to DISPLAY interface
Via the CAN bus interface on a system centre / store computer / operator terminal in the E*LDS-System.
11.1.9 Termination of alarm
The condition for termination of an alarm can be selected from two basic principles:
Automatic reset of all alarms after correcting the cause
Manual reset of all alarms after correcting the cause
The manual reset of the alarm / alarm state can be performed
By switching off the controller, regardless of whether the alarm is still active
On a local BT 300 x Operator Interface connected to the display port
Via the CAN bus interface using a system centre / store computer / operator terminal in the E*LDS-System.
11.1.10 Restart
During a restart old alarms are marked with a send time stamp.