![ECKELMANN UA 400 Operating Instruction Download Page 394](http://html2.mh-extra.com/html/eckelmann/ua-400/ua-400_operating-instruction_3927526394.webp)
Firmware V3.15
21.04.2021
394/401
•
•
If an alarm with a controller priority > 0 is pending and this priority is set to 0 before the alarm has
been marked as gone, the controller has no possibility to reset the alarm in the store computer.
Therefore, it is recommended after any change of alarm priorities to the value 0 to restart the
controller or ensure that the adjusted alarms are not active at the time of the adjustment.
If the case controller is used with store computers without extended priority allocation, the priorities
may only be allocated between 0..2 or "– " (see store computer operating manual for priority
allocation). In the case of incorrect parametrisation, the alarm signalling behaviour of the store
computer is undefined (particularly with regard to the assignment of priorities to alarm destinations).
This also applies for the refrigeration point priority.
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Page 244: ...Firmware V3 15 21 04 2021 244 401...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Page 372: ...Firmware V3 15 21 04 2021 372 401...