Firmware V3.15
21.04.2021
206/401
COOLING 1A POS: XXXXX
Entry
Default
Setpoint R2.1 XXX °C
Supply air temperature setpoint
-10..20
0 °C
Hystersis R2.1 X K
Supply air temperature hysteresis setpoint
1..8
4 K
Setpoint R4.1 XXX °C
Return air temperature setpoint for comparison
-10..20
4 °C
Hystersis R4.1 X K
Return air temperature hysteresis setpoint
1..8
2 K