Firmware V3.15
21.04.2021
174/401
•
•
9.2.2 Menu 1 Actual Values UA 111 D
ACT VALUES POS: XXXXX
1 Temp. Sensor
Move to menu 1-1
2 Cooling Zone 1
Move to menu 1-2
3 Defrost Zone 1
Move to menu 1-3
4
Not used with this controller type
5 Alarm
Move to menu 1-5
6 Frame Heater
Move to menu 1-6
Menu 1-1 Temp. Sensor
TEMPERATUR Pos: XXXXX
Temp. R2.1 xxx °C
Current supply air temperature Input Z11/ Z12
Temp. R4.1 xxx °C
Current return air temperature Input Z21/ Z22
Temp. R2.2 xxx °C
Current supply air temperature Input Z31/ Z32
Temp. R4.2 xxx °C
Current return air temperature Input Z41/ Z42
Temp. R2.3 xxx °C
Current supply air temperature Input Z51/ Z52
Temp. R4.3 xxx °C
Current return air temperature Input Z61/ Z62
Temp. R2.4 xxx °C
Current supply air temperature Input Z71/ Z72
Temp. R4.4 xxx °C
Current return air temperature Input Z81/ Z82
Temp. R2.5 xxx °C
Current supply air temperature Input Z91/ Z92
Temp. R4.5 xxx °C
Current supply air temperature Input Z01/ Z02
Menu 1-2 Cooling Zone 1
COOLING 1 Pos: XXXXX
Compressor 1 xxx
Current ON/OFF status Compressor 1
Comp Run Tm 1 xx %
Compressor 1 on time during last days (00:00 - 24:00 hours)
Comp. Starts 1 0
Compressor 1 actuations during last days
Compressor 2 xxx
Current ON/OFF status Compressor 2
Comp Run Tm 2 xx %
Compressor 2 on time during last days (00:00 - 24:00 hours)
Comp. Starts 2 0
Compressor 2 actuations during last days
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Page 244: ...Firmware V3 15 21 04 2021 244 401...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Page 372: ...Firmware V3 15 21 04 2021 372 401...