10. Fault tracing
When the option board or the AC drive control diagnostics
detect an unusual operating condition, the drive opens a
notification, for example, on the keypad. The keypad shows
the ordinal number of the fault, the fault code and a short
fault description.
You can reset the fault with the Reset button on the
control keypad, via the I/O terminal or via the used fieldbus
protocol. The faults are stored in the Fault history menu,
which can be browsed. The fault table presents only the
fault conditions related to the fieldbus in use.
otee:
N
When you contact a distributor or a factory because of
a fault condition, always write down all the texts and
codes on the keypad display. Then send the problem
description together with the Drive Info File to the
following address: [email protected].
If possible, also send a “Wireshark” log from the
situation if applicable.
10.1 Typical fault conditions
Table 155. Typical fault conditions
Fault condition
Possible cause
Remedy
Cabling
Supply or motor cables are
located too close to the
fieldbus cable
Wrong type of fieldbus cable
Too long cabling
Grounding
Inadequate grounding.
Ensure grounding in all
the points on the net.
Connections
Faulty connections: Excessive
stripping of cables
Faulty connections: Conductors
in wrong terminals
Faulty connections: Too loose
connections of conductors
Parameter
Faulty address
Overlapping slave addresses
Wrong control place selected
10.2 Other fault conditions
The following fault tracing diagram will help you to locate
and fix some of the most usual problems. If the problem
persists, contact your local distributor.
Figure 34. Fault tracing diagram for OPTE9
Drive does not
start from the
bus
Check
communication
status
Is device in
READY state?
Is fieldbus
selected as control
place in drive?
Does Master
give RUN
command?
Use
datalogger or
keypad to
monitor
variable
Counter does
not run
Check the
option board
LEDs
Check
parameter
(M1, 15 or
P3.2.1)
Counter for bad
frames
increases
Check drives
external
interlockings
(I/O)
Counter OK
No
communication
Check fieldbus
parameters
Check selected
protocol
Check other
fieldbus
parameters
in menu
Check
Master’s
parameters
Check IP
settings
Poor
communication
Check cabling
Check
connections
Check distance
between cables
Check cable
types and
lengths
Check
stripping of
cables and
conductors
Check
e.g. WLAN or
other routers
Check cabling
Check cable
for outs
Check correct
placement of
conductors
inteminals
Other bus
devices
Other bus
devices