22
7. Modbus TCP
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
7.1.3.5.6. Resettable operation day counter
This register holds the value for resettable control unit
operating time counter (trip value). The values are read only.
For resetting this counter see Chapter 7.1.3.2 “Clearing
resettable counters”.
Resettable operation day counter as seconds
This counter in registers 40111d to 40112d holds the
value of resettable operation days as seconds in a 32-bit
unsigned integer.
Table 26. Resettable operation days counter as seconds
Address
Description
40111 High data
40112 Low data
Holds the counter value as seconds.
Resettable operation day counter
This counter in registers 40101d to 40105d holds the value
of operation days counter.
Table 27. Resettable operation day counter
Holding register
addres
Input register
address
Purpose
40101
101
Years
40102
102
Days
40103
103
Hours
40104
104
Minutes
40105
105
Seconds
7.1.3.5.7 Energy counter
This counter holds the value of total amount of energy
taken from a supply network. This counter cannot be reset.
The values are read only.
Energy counter as kWh
This counter is in registers 40211d to 40212d and is a 32-bit
floating point (IEEE 754) value containing the number of
kilowatt-hours (kWh) that is in the drive’s energy counter.
This value is read-only.
Table 28. Energy counter as kWh
Address
Description
40211 High data
40212 Low data
Holds the value of energy counter in kWh.
Datatype is 32 bit
float IEEE 754
Energy counter
These registers hold three values for the energy counter,
amount of energy used, format of the energy value and unit
of the energy value.
Examplee:
If energy = 1200, format = 52, unit = 1, then
actual energy is 12.00 kWh.
Table 29. Energy counter
Holding
register
address
Input
register
address
Purpose
Description
40201
201
Energy
Amount of energy taken from a
supply network.
40202
202
Format
The last number of the Format
field indicates the decimal
point place in the Energy field.
Example:
40 = 4 number of digits, 0
fractional digits
41 = 4 number of digits, 1
fractional digit
42 = 4 number of digits, 2
fractional digits
40203
203
Unit
1 = kWh
2 = MWh
3 = GWh
4 = TWh
Unit of the value.
7.1.3.5.8. Resettable energy counter
This counter holds the value of total amount of energy
taken from a supply network since the counter was
last reset. For resetting this counter see Chapter 7.1.3.2
“Clearing resettable counters”. The values are read only.
Resettable energy counter as kWh
This counter is in registers 40311d to 40312d and is a
32-bit floating point (IEEE 754) value containing the number
of kilowatt-hours (kWh) that is in the drive’s resettable
energy counter.
Table 30. Resettable energy counter as kWh
Address
Description
40311 High data
40312 Low data
Holds the value of energy counter in kWh since last
counter reset. Datatype is 32 bit float IEEE 754
Resettable energy counter
These registers hold three values for the energy counter,
amount of energy used, format of the energy value and unit
of the energy value.
Examplee:
If energy = 1200, format = 52, unit = 1, then
actual energy is 12.00 kWh.