34
8. Profinet IO
Dual port ethernet option board installation manual
MN032004EN October 2017 www.eaton.com
8.4.1.2 PROFIDrive signal numbers in OPTE9
The table below lists the PROFIDrive signal numbers.
Table 63. PROFIDrive signal numbers
Signal no.
Signal name
PNU
PNU name
1
Control word 1
10100
PROFIDrive control word (STW1)
2
Status word 1
10102
PROFIDrive status word (ZSW1)
5
Speed setpoint A
10101
PROFIDrive speed setpoint value (NSOLL_A)
6
Speed actual value A
10103
PROFIDrive speed actual value (NIST_A)
51
Output current
10104
Always returns zero.
52
Active current (torque proportional)
10105
Always returns zero.
54
Active power
10106
Always returns zero.
57
Speed actual value A
10107
Always returns zero.
58
Drive status/fault word
10108
Always returns zero.
* 32 bit data not supported in current version. See chapter 5.