63
User Manual
MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON
www.eaton.com
Table 102. Register Definitions for S811+ Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name
Description
(Units)
- 614 R/W
Kickstart
Duration
The amount of time to apply a kick start
0.0 - 2.0 (in 0.1secs)
- 615 R/W
Ramp2
Expected
Phase
Sequence
Expected phase sequence of incoming
mains for ramp2 start
0 - ABC
1 - ACB
- 616 R/W
Ramp2
Motor
Start Method
Motor start method for ramp2 start
0x00 - rampstart (voltage ramp)
0x01 - current limit (applies a constant
voltage during start)
0x02 - reserved
0x03 - pumpstart (when selected, ramp2
pumpstop is active, ramp2 softstop is
not active)
- 617 R/W
Ramp2
Initial
Starting
Torque
Starting torque setting for ramp2 start
- 618 R/W
Ramp2
Start
Ramp Time
Motor start ramp time for ramp2.
- 619 R/W
Ramp2
Stop
Ramp Time
Motor stop ramp time for ramp2.
Parameter is not active when ramp2
start method is set to pump
- 620 R/W
Ramp2
Pump
Stop Time
The amount of time to use for the pump
stop ramp2 behavior. Parameter is
active when pumpstart is selected for
ramp2 motor start method
- 621 R/W
Ramp2
Kickstart
Starting
Torque
Initial torque value for the kick start
for ramp2
- 622 R/W
Ramp2
Kickstart
Duration
The amount of time to apply a kick start
0.0 - 2.0 (in 0.1secs) for ramp2 start
9953 623
R/W Local
Control
Only Enable
Local control from terminal block enable
0x00 - disabled (network control pos-
sible)
0x01 - enabled (local control from termi-
nal block only)
- 624 R/W
Discrete
Input
Cfg
Allows custom configuration of the
S811+ inputs#1 - #4 and four additional
network inputs
0 - no function
1 - run1
2 - ramp2
3 - jog
4 - local control enable
5 - fault reset
6 - e-stop input (active low)
7 - alarm no trip (active low)
8 - external fault (active low)
9 - external warning (active low)
10 - disable overload on start
11 - analog input enable (only for
input#4)
- 632 R/W
Analog
Input
Data Range
Selected range of analog input
0x02 0-20mA range
0x03 4-20mA range
- 633 R/W
Discrete
Output Cfg
Allows custom configuration of the two
S811+ aux relays and two additional
network outputs
0 - no function
1 - faulted
2 - not faulted
3 - in bypass
4 - not in bypass
5 - motor is energized
6 - motor is not energized
7 - warning
8 - not warning
9 - custom code (up to 3 specific codes
can be entered to trip this output)
10 - not custom code
Table 102. Register Definitions for S811+ Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name
Description
(Units)
- 637 R/W
Custom
Fault
Output Cfg
User can select up to 3 specific fault/
warning codes which will be used to
trip any outputs configured for “custom
codes”
- 640 R/W
Fault
Reset
Mode
Fault reset mode
0x00 - manual reset
0x01 - auto reset
0x02 - power on reset (reset faults on
power cycle)
- 641 R/W
Auto
Reset
Delay Time
Delay time after fault before attempting
to auto reset
- 642 R/W
Auto
Reset
Attempt Limit
Max number of auto reset attempts;
once reached, S811 requires manual
reset to clear fault
- 643 R/W
Overload
Trip
Enable
Motor overload trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
10289 644
R/W Enable
Overload
During Start
Enable the overload during start ramp
0x00 - overload is disabled during start
ramp
0x01 - overload is enabled during start
ramp
- 645 R/W
Phase
Reversal Trip
Enable
Phase reversal trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 646 R/W
Undercurrent
Trip Enable
Low load current trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 647 R/W
Undercurrent
Trip Level (%
FLA)
Low load current trip threshold in per-
cent of the motor nameplate fla setting
- 648 R/W
Undercurrent
Trip Duration
Amount of time a low current condition
must exist before a trip; 0.0 - 60.0 (in
0.1secs)
- 649 R/W
Motor
Jam
Trip Enable
Motor jam trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 650 R/W
Motor
Stall
Trip Enable
Motor stall trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 651 R/W
Phase
Loss
Trip Enable
Motor phase loss trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 652 R/W
Motor
Phase
Loss Trip Level
Current phase loss trip threshold
- 653 R/W
Motor
Phase
Loss Duration
Amount of time a phase loss condition
must exist before a trip; 0.0 - 60.0 (in
0.1secs)
- 654 R/W
Phase
Imbalance Trip
Enable
Current phase imbalance trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 655 R/W
Motor
Phase
Imbalance Trip
Level
Current imbalance trip threshold
- 656 R/W
Motor
Phase
Imbalance Trip
Duration
Amount of time a current imbalance
condition must exist before a trip; 0.0 -
60.0 (in 0.1secs)
- 657 R/W
Voltage
Imbalance Trip
Level
Voltage imbalance trip threshold
- 658 R/W
Voltage
Imbalance Trip
Duration
Amount of time a voltage imbalance
condition must exist before a trip; 0.0 -
60.0 (in 0.1secs)