43
User Manual
MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON
www.eaton.com
Table 84. Class 41 (0x29): Control Supervisor Object
Instance Count: 1
Instance List: 1
Attrib NV
Access
Data
Type Name
Description
3 (0x03)
V
Set/Get BOOL
Run1
Run the softstarter.
4 (0x04)
V
Set/Get BOOL
Run2
Run the softstarter(ramp2)
7 (0x07)
V
Get
BOOL
Running1
Indicates if the motor is run-
ning standard ramp
8 (0x08)
V
Get
BOOL
Running2
Indicates if the motor is run-
ning ramp2
9 (0x09)
V
Get
BOOL
Ready
Softstarter is not faulted
10 (0x0A)
V
Get
BOOL
Faulted
Fault present
11 (0x0B)
V
Get
BOOL
Warning
Warning present
12 (0x0C)
V
Set/Get BOOL
Fault Reset
Reset Fault
15 (0x0F)
V
Get
BOOL
Control From
Net
Control is coming from the
network.
22 (0x16)
V
Get
UDINT Total motor
starts
Total Motor Starts
100 (0x64) NV
Set/Get USINT S811 Input1 cfg Entry 1
101 (0x65) NV
Set/Get USINT S811 Input2 cfg Entry 2
102 (0x66) NV
Set/Get USINT S811 Input3 cfg Entry 3
103 (0x67) NV
Set/Get USINT S811 Input4 cfg Entry 4
104 (0x68) NV
Set/Get USINT C441 Input1 cfg Entry 5
105 (0x69) NV
Set/Get USINT C441 Input2 cfg Entry 6
106 (0x6A) NV
Set/Get USINT C441 Input3 cfg Entry 7
107 (0x6B) NV
Set/Get USINT C441 Input4 cfg Entry 8
108 (0x6C) NV
Set/Get USINT S811 FormA
relay cfg
Entry 1
109 (0x6D) NV
Set/Get USINT S811 FormC
relay cfg
Entry 2
110 (0x6E) NV
Set/Get USINT C441 Output1
relay cfg
Entry 3
111 (0x6F) NV
Set/Get USINT C441 Output2
relay cfg
Entry 4
112 (0x70) NV
Set/Get UINT
Custom fault
code 1
Entry 1
113 (0x71) NV
Set/Get UINT
Custom fault
code 2
Entry 2
114 (0x72) NV
Set/Get UINT
Custom fault
code 3
Entry 3
115 (0x73) NV
Set/Get BOOL
Terminal Block
control enable
Enables Local control at the
terminal block
116 (0x74) V
Get
BOOL
Run1 logic
sense
Status of Run1 input logic
sense (edge/level)
117 (0x75) NV
Set/Get BOOL
wiring config
0 - standard wiring; 1 -
Inside the delta wiring
118 (0x76) NV
Set/Get BOOL
Pending start
warning
Enables warning when
start delay timers are used.
Warning is issued while
start command is pending
119 (0x77) NV
Set/Get UINT
Power up start
delay
Time delay after power up
before a start command can
be issued
120 (0x78) NV
Set/Get UINT
Start delay
Time delay after a start com-
mand is issued before the
S811+ will attempt start
121 (0x79) NV
Set/Get UINT
Run cmd start
delay
User settable time delay
between successive
start profiles. Delay
becomes active when start
profile(ramp vs ramp2)
changes between starts
122 (0x7A) V
Get
UINT
Auto Reset
Count
Number of auto reset
attempts
Table 83. Class 10 (0x0A): Analog Input Object
Instance Count: 1
Instance List: 1
Attrib NV
Access
Data
Type Name
Description
3 (0x03) V
Get
USINT Analog Input
Value (% of
range)
Analog input reading (in percent of
set range)
8 (0x08) V
Get
USINT Analog Value
Data Type
Analog Input Value Data Type
0 - INT
1 - REAL
2 - USINT
3 - SINT
4 - DINT
5 - LINT
6 - UINT
7 - UDINT
8 - ULINT
9 - LREAL
100 - (Vendor specific) USINT -
Value in % of selected range (only
format supported)
100
(0x64)
V Get USINT
Analog
Input
Status
Status of the S811+ analog input
0x00 - Not Active
0x01 - Input under range
0x02 - Input over range
0x03 - Input in overdrive
0x04 - Input is in range
101
(0x65)
NV Set/Get USINT Analog
Input
Data Range
Selected range of analog input
0x02 0-20mA range
0x03 4-20mA range
102
(0x66)
NV Set/Get USINT Analog
Input
Trip Enable
Analog input trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
103
(0x67)
NV Set/Get USINT Analog
Input
Trip Low
Threshold
Low analog input trip threshold (in
percent of selected analog range)
104
(0x68)
NV Set/Get USINT Analog
Input
Trip High
Threshold
High analog input trip threshold (in
percent of selected analog range)
105
(0x69)
NV Set/Get UINT Analog
Input
Trip Duration
Amount of time a low or high
analog input condition must exist
before a trip; 0.0 - 60.0 (in 0.1secs)