46
User Manual
MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON
www.eaton.com
Table 86. Class 45 (0x2D): Softstart Object (Cont.)
Attrib NV Access
Data
Type Name
Description
114
(0x70)
NV Set/Get USINT
Temperature
Sensor Trip
Enable
Temperature sensor trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
115
(0x71)
NV Set/Get USINT
SCR
Not
Firing Trip
Enable
SCR not firing trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
116
(0x72)
NV Set/Get USINT
SCR
Shorted
Trip Enable
Shorted SCR trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
Table 87. Class 140 (0x8C): Device Status Object
Instance Count: 1
Instance List: 1
Attrib NV Access
Data
Type Name Description
1
(0x01)
V Get USINT
Motor
status
Motor Control Status Word for S811+
Bit Description
0 Running1 - RUN1 command active
1 Running2 - Jog command active
2 Permissive - Start allowed
(must be 1 to start)
3 Ramp2 - Ramp2 settings active
4 Local Control (0 - network; 1 - local)
5 Faulted - S811+ fault present
6 Warning - S811+ warning present
(self clearing)
7 In bypass - S811+ Bypass closed
2
(0x02)
V Get USINT
S811
input
status
The Discrete data Input register will show
the active/inactive status of S811+ hard-
wired and networked inputs. Bits 3..0 indi-
cate the status of the S811+ terminal block
inputs and bits 7..4 indicate the status of
the network inputs located in the Network
Data Input Register (C441 communication
adapter inputs#1- 4 when connected)
Bit Description
0 S811+ discrete input#1 status
1 S811+ discrete input#2 status
2 S811+ discrete input#3 status
3 S811+ discrete input#4 status
4 Network input#1 status
( C441 Com adapter input#1)
5 Network input#2 status
( C441 Com adapter input#2)
6 Network input#3 status
( C441 Com adapter input#3)
7 Network input#4 status
( C441 Com adapter input#4)
3
(0x03)
V Get USINT
S811
output
status
The Discrete data Output register bits 1..0
indicate the status of the S811+ relays and
bits 3..2 indicate the status of the network
outputs being generated by the S811+ con-
figurable output logic(C441 communication
adapter outputs#1- 2 when connected)
Bit Description
0 S811+ discrete formA relay status
1 S811+ discrete formC relay status
2 Network output#1 status
( C441 Com adapter output#1)
3 Network output#2 status
( C441 Com adapter output#2)
4
5
6
7
4
(0x04)
V Get UINT Active
Fault #1
Will display up to 3 faults/warnings that
are actively present
5
(0x05)
V Get UINT Active
Fault #2
Will display up to 3 faults/warnings that
are actively present
6
(0x06)
V Get UINT Active
Fault #3
Will display up to 3 faults/warnings that
are actively present
7
(0x07)
V Get UINT Bit
field
(faults)
S811+ Motor Control Fault Bit Field
Bit Fault
0 Phaseloss
1 Phase Imbalance
2 Thermal Pile
3 Overcurrent
4 Breaker Fault
5 GND Fault
6 Motor Stall
7 Motor Jam
8 OverTemp
9 UnderLoad
10 Reserved
11 Estop
12 Reserved
13 Reserved
14 Reserved
15 Other