Table 31. Overload Object Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name
Description
113 NV
Set/Get
UINT Motor
Fault
Number of
Restarts
Motor Fault Number of Attempts:
0: Manual
1-4
5: Automatic
114 NV
Set/Get
UINT Run
Transition
Time
Run Transition Time (sec)
115 NV
Set/Get
UINT Run
Transition
Percent
Run Transition % of FLA (%)
116 NV
Set/Get
UINT Ground
Fault Trip
Mode
Ground Fault Trip Mode
0 - Trip on Ground Fault
1 - Alarm No Trip
117 NV
Set/Get
UINT Ground
Fault Trip
Delay
Ground Fault Pickup Delay (sec)
118 NV
Set/Get
UINT Ground
Fault Pick-
up Level
Ground Fault Pick-up Level (x0.01A)
119 NV
Set/Get
UINT Current
Unbalance
Trip Delay
Current Unbalance Trip Delay (sec)
120 NV
Set/Get
UINT Current
Unbalance
Pick-up
Level
Current Unbalance Pick-up Level (%)
121 NV
Set/Get
UINT Jam
Trip
Delay
Jam Trip Delay (sec)
122 NV
Set/Get
UINT Jam
Pick-
up Level
Jam Pick-up Level (%)
123 NV
Set/Get
UINT Current
Phase Loss
Trip Delay
Pickup Delay for Current Phase Loss
(sec)
124 NV
Set/Get
UINT High
KW
Trip Time
High Power Trip Delay (sec)
125 NV
Set/Get
UINT High
KW
Trip limit
High Power Pick-up Level (x0.01kW)
126 NV
Set/Get
UINT Low
Power
Trip Delay
Low Power Trip Delay (sec)
127 NV
Set/Get
UINT Low
Power
Pick-up
Level
Low Power Pick-up Level (x0.01kW)
128 NV
Set/Get
UINT Under
Current Trip
Delay
Under Current Trip Delay (sec)
129 NV
Set/Get
UINT Under
Current
Pick-up
Level
Under Current Pick-up Level (%)
130 NV
Set/Get
UINT Overload
Reset
Overload Reset Mode
0: Manual Reset
1: Apply Motor Fault Reset Delay and
Number of Attempts
131 NV
Set/Get
UINT Load
Fault
Reset
Delay Calc
Load Fault Reset Delay Calculator
Enable.
Value = Description
0 = Disable (default)
1 = Enabled
132
NV Set/Get BOOL Overload
on Start
Enable
0 = Disable
1 = Enable
133
NV
Set/Get BOOL
GF on Start
Enable
0 = Disable
1 = Enable
Supported by CP and HVR only.
Voltage Monitor Object
Class 147 (0x93):
Instance Count: 1
Instance List: 1
Table 32. Voltage Monitor Object Instance Attributes
Attrib
NV Access
Data
Type Name
Description
1
V
Get
UINT Voltage L1-L2
Phase A RMS Voltage L1-L2 (V)
2
V
Get
UINT Voltage L2-L3
Phase B RMS Voltage L2-L3 (V)
3
V
Get
UINT Voltage L3-L1
Phase C RMS Voltage L3-L1 (V)
4
V
Get
UINT Voltage Average Average RMS Voltage (V)
5 V
Get UINT
Voltage
Unbalance
Percentage
Max Deviation from Average
Voltage Divided by Average
Voltage (%)
6
V
Get
UINT Line Frequency
Line Frequency (x0.01Hz)
7 NV
Set/Get
UINT
Voltage
Faults
Trip Mode
Voltage Faults Trip Mode
0 - Trip On Supply Fault
1: Alarm-no-Trip (Inhibit Start)
8 NV
Set/Get
UINT
Under
Voltage
Pick-up Level
Under Voltage Pick-up Level (V)
9 NV
Set/Get
UINT
Under
Voltage
Trip Delay
Under Voltage Trip Delay (sec)
10 NV
Set/Get
UINT
Over
Voltage
Pick-up Level
Over Voltage Pick-up Level (V)
11
NV Set/Get UINT Over Voltage Trip
Delay
Over Voltage Trip Delay (sec)
12 NV
Set/Get
UINT
Voltage
Unbalance
Pick-up Level
Voltage Unbalance Pick-up Level
(%)
13 NV
Set/Get
UINT
Voltage
Unbalance
Trip Delay
Voltage Unbalance Run Delay (sec)
14
NV Set/Get UINT Phase Order
Phase Order
- 0 (Trip Disabled)
- 1 ACB
- 2 ABC
15 NV
Set/Get
UINT
Supply
Fault
Hold-off Time
Restart Delay (sec)
16 V
Get UINT
Remaining
Rapid
Cycling Restart
Delay
Supply Fault - Time to Restart (sec)
100
NV Set/Get UINT Wire Config
0 = Three-phase
1 = Single-phase voltage and
current
2 = Three-phase current only
101
NV Set/Get UINT PT Ratio
Indicates a PT ratio:120 step-down
Range = 0 to 8000, 0 indicates no
PT connection
TCP/IP Interface Object
Class 245 (0xF5):
Instance Count: 1
Instance List: 1
Table 33. Object Attributes
Attrib
NV Access
Data
Type Name
Description
13
NV
Set/Get UINT Encapsulation
Inactivity
Timeout
Number of seconds of inactivity
before TCP connection is closed