7.3 Register Definition for the C440 Overload Relay
Table 100. Registers for the C440 Overload Relay
Start
Coil
Register
Read/
Write
Name
Description (Units)
1
1
R
Field Inputs
A Bitfield Representing the Input Points.
Bit = Description
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
- 2
R Control
Voltage
Adapter Source Voltage. ( mV )
- 3
R Ambient
Temperature
Device Ambient Temperature as
Measured from the PCB. ( ºC )
- 4
R/W
Max
Board
Temperature
The maximum board temperature experi-
enced since manufacturing. ( ºC )
65 5
R Dip
Switch
Value
A bit field representing the present state
of the dip switches.
- 6
R Configuration
CRC
A CRC value calculated over the non-
volatile data present.
-
7
R/W
Serial Number 32 bit Com Adapter Device Serial
Number.
-
9
R
Firmware Rev
Com Adapter Firmware Rev.
-
11
R/W
Hardware Rev Com Adapter Hardware Rev.
1601 101
R/W Field
Relay
Outputs
A Bitfield Representing the Output Points.
Bit = Description
0 = Output 1
1 = Output 2
- 102 R/W
Field
Inputs
Debounce
Array of Debounce Values. A debounce
value exists for each input. The
debounce applies to both rising and fall-
ing edge. ( milliseconds )
- 110 R/W
Modbus
TCP
Com Timeout
Communication Timeout for Modbus TCP.
0 = Disable. ( milliseconds )
1761 111
R/W Field
Relay
Fault Action
When a communication fault occurs the
relays can execute two types of behavior.
The behavior is selected on a per bit
basis.
Bit = Description
0 = Relay 1
1 = Relay 2
Bit Value = Description
0 = Apply Fault Value
1 = No Change
1777 112
R/W Field
Relay
Fault State
Communication fault value to be applied.
A bitfield where each bit defines an
output point.
Bit Value = Description
0 = Turn Relay Off
1 = Turn Relay On
1793 113
R/W Field
Relay
Idle Action
When a communication idle state occurs
the relays can execute two types of
behavior. The behavior is selected on a
per bit basis.
Bit = Description
0 = Relay 1
1 = Relay 2
Bit Value = Description
0 = Apply Idle Value
1 = No Change
1809 114
R/W Field
Relay
Idle State
Communication idle value to be applied.
A bitfield where each bit defines an
output point.
Bit Value = Description
0 = Turn Relay Off
1 = Turn Relay On
-
143
R
Method of IP
Allocation
The Method Used to Allocate an IP
Address:
0 - DHCP
1 - Upper three octets from NV and lower
octet selected by the dip switch setting.
2 - Full address taken from NV Memory.
3 - Restore (hardcoded 192.168.1.254).
Table 100. Registers for the C440 Overload Relay (Cont.)
Start
Coil
Register
Read/
Write
Name
Description (Units)
- 144 R Present
Ethernet IP
Address
The active IP address being used on the
network.
- 146 R Present
Ethernet
Subnet Mask
The active subnet mask IP address being
used on the network.
- 148 R Present
Ethernet
Default
Gateway
The active default gateway IP address
being used on the network.
- 150 R/W
Stored
Ethernet IP
Address
The IP address used in the NV address
select configuration.
- 152 R/W
Stored
Ethernet
Subnet Mask
The IP subnet mask used in the NV
address select configuration.
- 154 R/W
Stored
Ethernet
Default
Gateway
The IP default gateway used in the NV
address select configuration.
- 156 R/W
Ethernet
MAC
Address
-
3201 201
R
Intercom
Status
Present State of the Intercom Link.
Bit - Status
0 - Connected fully. No error messages.
1 - A message fault occurred.
2 - Devices are married. Target is identi-
fied and correct.
3 - A basic connection is established.
4001 251
R/W Motor
Ctrl
Idle Loss Act
Disable
When this value is TRUE the motor state
will be unchanged after a communication
idle event. A FALSE value will cause the
Motor Control Communication Idle Value
to be applied on a com idle event.
4017 252
R/W Motor
Ctrl
Com Idle
Action Val
Action to execute when a communication
loss event occurs.
0 = Ignore (No Change)
1 = Stop
4033 253
R/W Motor
Ctrl
Com Loss Act
Disable
When this value is TRUE the motor state
will be unchanged after a communication
loss event. A FALSE value will cause the
Motor Control Communication Loss Value
to be applied on a com loss.
4049 254
R/W Motor
Ctrl
Com Loss
Action Val
Action to execute when a communication
loss event occurs.
0 = Ignore (No Change)
1 = Stop
- 255
R/W
EtherNet/
IP Comm
Timeout
EtherNet/IP communication timeout
Range: 0–60,000 ms
Default: 3000 ms
- 256
R/W
Encapsu-
lation
Inactivity
Timeout
Number of seconds of inactivity before
TCP connection is closed
- 300 R Motor
Ctrl
State
Motor Control States:
0 = Stopped
1 = Running
2,3 = Tripped
4 = Resetting
- 301 R Scaled
Current
Phase A RMS
Scaled RMS Current Phase A ( Amps )
- 302 R Scaled
Current
Phase B RMS
Scaled RMS Current Phase B ( Amps )
- 303 R Scaled
Current
Phase C RMS
Scaled RMS Current Phase C ( Amps )
- 304 R Scaled
3Phase
Ave Current
Average of the 3 Scaled RMS Currents
( Amps )
- 305 R Thermal
Memory
Percentage
Present Thermal Value. 100% equates to