30
User Manual
MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON
www.eaton.com
Table 53. S611 Assembly Instance 105 (0x69): Basic Overload w/
Relay
Byte
Offset
Word
Offset
Size
(bytes) Name
Description
0 0 1 Basic
Overload w/
Relay
Basic Overload with Relays
Bit = Description
Bit 0 = Relay Output 1
Bit 1 = Relay Output 2
Bit 2 = Fault Reset
Total Assembly Size (bytes): 1
Table 54. S611 Assembly Instance 106 (0x6A): Extended Motor
Ctrl
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 1 Extended
Motor
Ctrl
Extended Motor Control
Bit = Description
0 = Run 1
1 = Permissive
2 = Fault Reset
6 = Output 1
7 = Output 2
Total Assembly Size (bytes): 1
Table 55. S611 Assembly Instance 107 (0x6B): Extended
Overload w/ IO
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 1 Extended
Overload
w/ IO
Extended Overload Assembly with IO.
Bit = Description
0 = Fault
2 = Output 1
3 = Output 2
4 = Input 1
5 = Input 2
6 = Input 3
7 = input 4
Total Assembly Size (bytes): 1
Table 56. S611 Assembly Instance 108 (0x6C): Motor Ctrl Status
w/IO
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Motor
Ctrl
Status
w/IO
Motor Control Status Input Assembly.
Bit = Description
0 = Fault
1 = Bypass
2 = Running 1
3 = S611 Run/Aux Relay
4 = S611 Fault Relay
5 = Control From Net
6 = Permissive
8 = Output 1
9 = Output 2
10 = Input 1
11 = Input 2
12 = Input 3
13 = Input 4
15 = S611 Internal Com Lost
Total Assembly Size (bytes): 2
Table 57. S611 Assembly Instance 121 (0x79): Status
Measurement and Thermal
Includes the motor Ave Current, Thermal value and Ave Voltage monitoring.
Word Size (bytes): 2.
All data is little endian (low byte first).
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Device
Status
Device Bit Array, Bit:
0: Fault
1: Bypass
2: Running1
3: S611 Run/Aux Relay (Relay 1)
4: S611 Fault Relay (Relay 2)
5: CtrlFromNet
6: Permissive
7: Reserved
8: Output #1
9: Output #2
10: Input #1
11: Input #2
12: Input #3
13: Input #4
14: DeviceNet Low Power
15: S611 Intercom Lost
2 1 2 Average
Current
Average of the 3 Scaled RMS Currents.
(Amps)
4 2 2 Average
Voltage
Average of the 3 Scaled RMS Voltages
(Volts)
6 3 2 Trip
Reason
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
Total Assembly Size (bytes): 8