21
User Manual
MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON
www.eaton.com
Table 30. C441 Motor Insight Control Supervisor Instance
Attributes
Attrib NV Access
Data
Type Name Description
10 V
Get BOOL
Fault
Status
A Fault has occurred. Faults are latch-
ing and require a reset.
11 V
Get BOOL
Warning
Status
A Warning has occurred. Warnings
self clear.
12 V
Set/Get
BOOL
Fault
Reset
0->1 Causes a reset.
13 V
Get UINT
Fault
Queue
Fault Code and Fault Code List.
When read as a single item it is the
most recent fault.
When read as a list, faults are listed in
history order.
Newest are at the beginning, oldest are
at the end of the list.
If the device is in the Faulted state,
Fault Code indicates the fault that
caused the transition to Faulted state.
If not in the Faulted state, the Fault
Code indicates the fault that caused the
last transition to the Faulted state.
17 V
Set/Get
BOOL
Force
Fault
0->1 = Force Fault
0 = No action
101 V Get WORD
Device
Status
Device Bit Array
Bit 0: Trip
Bit1: Warn
Bit2: Output #1
Bit3: Output #2
Bit4: Input #1
Bit5: Input #2
Bit6: Input #3
Bit7: Input #4
Bit8: Overload Power Lost
Bit 9: Comm Adapter Low Voltage
102 V Get UINT Trip
Reason
0x0001 - Restart Attempts Exceeded
0x0002 - Relay Turned Off (Network/UI)
0x0004 - Contactor Failure
0x0008 - Under Current Trip
0x0010 - Overload Trip
0x0020 - GND Fault Trip
0x0040 - Current Unbalance Trip
0x0080 - Current Single Phase
0x0100 - Reserved (0)
0x0200 - High Power Trip
0x0400 - Over Voltage Trip
0x0800 - Under Voltage Trip
0x1000 - Voltage Unbalance Trip
0x2000 - Over Current Trip
0x4000 - Low Power Trip
0x8000 - Phase Reversal Trip
103 V Get UINT Overload
Status
Overload Status
- 0x0001: Overload Trip
- 0x0002: Ground Fault Trip
- 0x0004: High Power Trip
- 0x0080: Relay Closed
104 V Get UINT Error
Code
Warning/Alarm Indications
0x0001 (1) - Low Voltage Warning
0x0002 (2) - High Voltage Warning
0x0004 (4) - Voltage Unbalance Warning
0x0008 (8) - Low Power Warning
0x0010 (16) - Reverse Phase Warning
0x0020 (32) - Current Unbalance
Warning
0x0040 (64) - Voltage Single Phase
Warning
0x0080 (128) - Current Single Phase
Warning
0x0100 (256) - GND Fault Warning
105 NV
Set/Get
BOOL
Motor
Ctrl Idle
Loss Act
Disable
When this value is TRUE the motor
state will be unchanged after a commu-
nication idle event. A FALSE value will
cause the Motor Control Communication
Idle Value to be applied on a com idle
event.
Table 30. C441 Motor Insight Control Supervisor Instance
Attributes (Cont.)
Attrib NV Access
Data
Type Name Description
106 NV
Set/Get
BOOL
Motor
Ctrl Com
Idle
Action
Val
Action to execute when a communica-
tion loss event occurs.
0 = Ignore (No Change)
1 = Stop
107 NV
Set/Get
BOOL
Motor
Ctrl Com
Loss Act
Disable
When this value is TRUE the motor
state will be unchanged after a commu-
nication loss event. A FALSE value will
cause the Motor Control Communication
Loss Value to be applied on a com loss.
108 NV
Set/Get
BOOL
Motor
Ctrl Com
Loss
Action
Val
Action to execute when a communica-
tion loss event occurs.
0 = Ignore (No Change)
1 = Stop
109 V Get UINT Fault
Queue
Fault Code and Fault Code List.
When read as a single item it is the
most recent fault.
When read as a list, faults are listed in
history order.
Newest are at the beginning, oldest are
at the end of the list.
If the device is in the Faulted state,
Fault Code indicates the fault that
caused the transition to Faulted state.
If not in the Faulted state, the Fault
Code indicates the fault that caused the
last transition to the Faulted state.
110 V Get UINT Fault
Queue
Entry 1
111 V Get UINT Fault
Queue
Entry 2
112 V Get UINT Fault
Queue
Entry 3
113 V Get UINT Fault
Queue
Entry 4
114 V Get UINT Fault
Queue
Entry 5
115 V Get UINT Fault
Queue
Entry 6
116 V Get UINT Fault
Queue
Entry 7
117 V Get UINT Fault
Queue
Entry 8
118 V Get UINT Fault
Queue
Entry 9
119 V Set/Get
BOOL
Clear
Last Fault
Entry
From
Queue
0->1 = Fault Entry Cleared
0 = No action
120 NV
Set/Get
UINT Enable/
Disable
Trip
Trip Enable/Disable Bit Array:
0x0001 (1): Enable Ground Fault
0x0002 (2): Enable Voltage Unbalance
0x0004 (4): Enable Current Unbalance
0x0008 (8): Enable Under Current
0x0010 (16): Enable Phase Loss
0x0020 (32): Enable Jam
0x0040 (64): Enable Low Power
0x0080 (128): Enable High Power
0x0100 (256): Enable Over Voltage
0x0200 (512): Enable Under Voltage
0x0400 (1024): Enable Phase Order