32
User Manual
MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON
www.eaton.com
Table 59. S611 Assembly Instance 133 (0x85): Full S611
Monitoring (Cont.)
Byte
Offset
Word
Offset
Size
(bytes) Name
Description
32
16
2
Trip Reason
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
34
17
2
Motor Status
Motor Control Status Bits:
Bit = Description
0 = Run
2 = In Bypass
5 = Fault
11 = Relay 1 State
12 = Relay 2 State
13 = Control From Network
14 = Permissive State
36
18
2
Pole Temp
Average Power Pole Temperature.
Scaled = x10 (°C).
38
19
2
Power Sign
Indicates Whether Power is Positive or
Negative. In the Case of a Generator.
40 20 2 Current
Scale
Factor
Scale Factor for Current. Use this Value
to Scale the Current Values.
42 21 2 Overload
Thermal
Memory
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip (%)
Total Assembly Size (bytes): 44
Class 8 (0x08): Discrete Input Object
Instance Count: 4
Instance List: 1, 2, 3, 4
Table 60. S611 Discrete Input Instance Attributes
Attrib NV Access
Data
Type Name
Description
101 NV
Set/Get
UDINT
Field
Inputs
Debounce
The debounce applies to both
rising and falling edge.
(milliseconds).
Class 9 (0x09): Discrete Output Object
Instance Count: 2
Instance List: 1, 2
Table 61. S611 Discrete Output Instance Attributes
Attrib NV Access
Data
Type Name Description
3 V
Set/Get
BOOL
Field
Relay
Outputs
Output Point Value.
Val = Description
0 = Off
1 = On
5 NV
Set/Get
BOOL
Field
Relay
Fault
Action
When a communication fault occurs
the output can execute two types of
behavior.
0 = Apply Fault Value
1 = No Change
6 NV
Set/Get
BOOL
Field
Relay
Fault
State
Communication fault value to be
applied.
Value = Description
0 = Turn Relay Off
1 = Turn Relay On
7 NV
Set/Get
BOOL
Field
Relay
Idle
Action
When a communication idle state
occurs the relays can execute two
types of behavior.
Value = Description
0 = Apply Idle Value
1 = No Change
8 NV
Set/Get
BOOL
Field
Relay
Idle
State
Communication idle value to be
applied.
Value = Description
0 = Turn Relay Off
1 = Turn Relay On