Table 68. Assembly Instance 60 (0x3C): Basic Softstarter Input
Byte Offset
Word
Offset
Size
(bytes) Name
Description
0
0 1 Basic
Softstarter
Input
Basic softstart Input.
Bit = Description
0 = Faulted
2 = Running1
7 = Bypass (at reference)
Total Assembly Size (bytes): 1
Table 69. Assembly Instance 61 (0x3D): Extended Softstarter
Input
Byte
Offset
Word
Offset
Size
(bytes) Name
Description
0
0 1 Extended
Softstarter
Input
Extended Softstart Input
Bit = Description
0 = Faulted
1 = Warning
2 = Running1
3 = Running2 (Ramp2)
4 = Ready
5 = CtrlFromNet
7 = Bypass (at reference).
Total Assembly Size (bytes): 1
Table 70. Assembly Instance 101 (0x65): Extended Softstarter
Output with Relay Outs
Byte Offset
Word
Offset
Size
(bytes) Name
Description
0
0 1 Extended
Softstarter
Extended softstart assembly w
relay outputs.
Bit = Description
0 = Run 1
1 = Run 2 (Ramp2)
2 = Fault Reset
4 = C441 Q1 relay out
5 = C441 Q2 relay out
Total Assembly Size (bytes): 1
Table 71. Assembly Instance 102 (0x66): Device Status
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Device
Status
Device Status Bit Array
0 Running - RUN command active
1 Jogging - Jog command active
2 Permissive - Start allowed (must be
1 to start)
3 Ramp2 - Ramp2 settings active
4 Local Control (0 - network; 1 - local)
5 Faulted - S811+ fault present
6 Warning - S811+ warning present
(self clearing)
7 In bypass - S811+ Bypass closed
8 = Output 1
9 = Output 2
10 = Input 1
11 = Input 2
12 = Input 3
13 = Input 4
14 = Alarm No Trip Enabled
15 = S811+ Internal Comm Loss
Total Assembly Size (bytes): 2
Table 72. Assembly Instance 110 (0x6E): Status and Current (A)
Assembly includes the status overview and motor current levels scaled in Amps.
Word Size (bytes): 2
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Device
Status
Device Status Bit Array
0 Running - RUN command active
1 Jogging - Jog command active
2 Permissive - Start allowed (must be
1 to start)
3 Ramp2 - Ramp2 settings active
4 Local Control (0 - network; 1 - local)
5 Faulted - S811+ fault present
6 Warning - S811+ warning present
(self clearing)
7 In bypass - S811+ Bypass closed
8 = Output 1
9 = Output 2
10 = Input 1
11 = Input 2
12 = Input 3
13 = Input 4
14 = Alarm No Trip Enabled
15 = S811+ Internal Comm Loss
2 1 6 3Ph
RMS
Line
Current
(amps)
Scaled RMS 3phase line current - This is
the actual current flowing to the motor
in 1.0A.
Total Assembly Size (bytes): 8
Table 73. Assembly Instance 111 (0x6F): Status and
Current (0.1A)
Assembly includes the status overview and motor current levels scaled in 0.1As.
Word Size (bytes): 2
Byte
Offset
Word
Offset
Size
(bytes) Name
Description
0
0
2
Device Status Device Status Bit Array
0 Running - RUN command active
1 Jogging - Jog command active
2 Permissive - Start allowed (must be
1 to start)
3 Ramp2 - Ramp2 settings active
4 Local Control (0 - network; 1 - local)
5 Faulted - S811+ fault present
6 Warning - S811+ warning present
(self clearing)
7 In bypass - S811+ Bypass closed
8 = Output 1
9 = Output 2
10 = Input 1
11 = Input 2
12 = Input 3
13 = Input 4
14 = Alarm No Trip Enabled
15 = S811+ Internal Comm Loss
2 1 6 3Ph
RMS
Line Current
(deciamps)
Scaled RMS 3phase line current - This is
the actual current flowing to the motor
in 0.1A.
Total Assembly Size (bytes): 8