Table 99. Registers Available with C441 Motor Insight (Cont.)
Start
Coil
Register
Read/
Write Name
Description (Units)
-
143
R
Method of IP
Allocation
The Method Used to Allocate an IP
Address:
0 - DHCP
1 - Upper three octets from NV and lower
octet selected by the dip switch setting.
2 - Full address taken from NV Memory.
3 - Restore (hardcoded 192.168.1.254).
- 144 R Present
Ethernet IP
Address
The active IP address being used on the
network.
- 146 R Present
Ethernet
Subnet Mask
The active subnet mask IP address being
used on the network.
- 148 R Present
Ethernet
Default
Gateway
The active default gateway IP address
being used on the network.
- 150 R/W
Stored
Ethernet IP
Address
The IP address used in the NV address
select configuration.
- 152 R/W
Stored
Ethernet
Subnet Mask
The IP subnet mask used in the NV
address select configuration.
- 154 R/W
Stored
Ethernet
Default
Gateway
The IP default gateway used in the NV
address select configuration.
- 156 R/W
Ethernet
MAC Address
-
- 159 R/W
Modbus
Com
Timeout
Communication Timeout for Modbus.
0 = Disable. ( milliseconds )
- 160 R/W
Modbus
TX
mode
Selects the Modbus Mode.
0 - RTU
1 - ASCII
- 161 R/W
Modbus
Baud
Rate
Selects the Modbus Baud Rate.
0 - 19.2kb
1 - 9.6kb
2 - 57.6kb
3 - 115.2kb
- 162 R/W
Modbus
Address
Modbus Address Loaded at Startup.
- 163 R/W
Modbus
Parity and
Stop Bits
Selects the Modbus UART Parity and
Stop Bits.
0 - Even/One Stop Bit
1 - Odd/One Stop Bit
2 - None/Two Stop Bits
3 - Even/Two Stop Bits
4 - Odd/Two Stop Bits
5 - None/One Stop Bit
3201 201
R
Intercom
Status
Present State of the Intercom Link.
Bit - Status
0 - Connected fully. No error messages.
1 - A message fault occurred.
2 - Devices are married. Target is identi-
fied and correct.
3 - A basic connection is established.
4001 251
R/W Motor
Ctrl
Idle Loss Act
Disable
When this value is TRUE the motor state
will be unchanged after a communication
idle event. A FALSE value will cause the
Motor Control Communication Idle Value
to be applied on a com idle event.
4017 252
R/W Motor
Ctrl
Com Idle
Action Val
Action to execute when a communication
loss event occurs.
0 = Ignore (No Change)
1 = Stop
4033 253
R/W Motor
Ctrl
Com Loss Act
Disable
When this value is TRUE the motor state
will be unchanged after a communication
loss event. A FALSE value will cause the
Motor Control Communication Loss Value
to be applied on a com loss.
Table 99. Registers Available with C441 Motor Insight (Cont.)
Start
Coil
Register
Read/
Write Name
Description (Units)
4049 254
R/W Motor
Ctrl
Com Loss
Action Val
Action to execute when a communication
loss event occurs.
0 = Ignore (No Change)
1 = Stop
- 255
R/W
EtherNet/
IP Comm
Timeout
EtherNet/IP communication timeout
Range: 0–60,000 ms
Default: 3000 ms
- 256
R/W
Encapsu-
lation
Inactivity
Timeout
Number of seconds of inactivity before
TCP connection is closed
-
300
R
Current I1
Phase A RMS Current, Unit:
90 Amp Models: x0.1A
9 Amp Models: x0.1A when external CTs
are used; x0.01A otherwise ( scale )
-
301
R
Current I2
Phase B RMS Current, Unit:
90 Amp Models: x0.1A
9 Amp Models: x0.1A when external CTs
are used; x0.01A otherwise ( scale )
-
302
R
Current I3
Phase C RMS Current, Unit:
90 Amp Models: x0.1A
9 Amp Models: x0.1A when external CTs
are used; x0.01A otherwise ( scale )
- 303 R Current
Average
Average RMS Current, Unit:
90 Amp Models: x0.1A
9 Amp Models: x0.1A when external CTs
are used; x0.01A otherwise ( scale )
-
304
R
Voltage L1-L2 Phase A RMS Voltage L1-L2 ( V )
-
305
R
Voltage L2-L3 Phase B RMS Voltage L2-L3 ( V )
-
306
R
Voltage L3-L1 Phase C RMS Voltage L3-L1 ( V )
- 307 R Voltage
Average
Average RMS Voltage ( V )
-
308
R
Motor Power Motor Power
x0.1kW when external CTs are used
x0.01kW otherwise ( scale )
- 309 R Voltage
Unbalance
Percentage
Max deviation from average voltage
divided by average voltage ( % )
- 310 R Current
Unbalance
Percentage
Max deviation from average current
divided by average current ( % )
- 311 R Apparent
Power Factor
cos(phi), (real power)/(apparent power)
( % )
- 312 R Residual
Ground
Current
Residual Ground Current in Amps x 100
( x0.01A )
- 313 R Line
fre-
quency
Line Frequency ( x0.01Hz )
- 314 R Thermal
Pile
Percentage
Thermal Capacity
0% Cold Motor
100% Will Cause and Overload Trip ( % )
-
315
R
Fault Queue
Fault Code and Fault Code List.
When read as a single item it is the most
recent fault.
When read as a list, faults are listed in
history order.
Newest are at the beginning, oldest are at
the end of the list.
If the device is in the Faulted state, Fault
Code indicates the fault that caused the
transition to Faulted state.
If not in the Faulted state, the Fault Code
indicates the fault that caused the last
transition to the Faulted state.
- 325 R Remaining
Rapid Cycling
Restart Delay
Supply Fault - Time to Restart ( sec )
- 326 R Remaining
Normal
Restart Delay
Motor Fault - Time to Restart ( sec )