Table 103. Registers Available when Used as Stand Alone I/O
(Cont.)
Start
Coil
Register
Read/
Write
Name
Description (Units)
-
143
R
Method of IP
Allocation
The method used to allocate an IP
Address:
0 - DHCP
1 - Upper three octets from NV and lower
octet selected by the dip switch setting.
2 - Full address taken from NV Memory.
3 - Restore (hardcoded 192.168.1.254).
- 144 R Present
Ethernet IP
Address
The active IP address being used on the
network.
- 146 R Present
Ethernet
Subnet Mask
The active subnet mask IP address being
used on the network.
- 148 R Present
Ethernet
Default
Gateway
The active default gateway IP address
being used on the network.
- 150 R/W
Stored
Ethernet IP
Address
The IP address used in the NV address
select configuration.
- 152 R/W
Stored
Ethernet
Subnet Mask
The IP subnet mask used in the NV
address select configuration.
- 154 R/W
Stored
Ethernet
Default
Gateway
The IP default gateway used in the NV
address select configuration.
- 156 R/W
Ethernet
MAC Address
-
- 230
R/W
EtherNet/
IP Comm
Timeout
EtherNet/IP communication timeout
Range: 0–60,000 ms
Default: 3000 ms
- 231
R/W
Encapsulation
Inactivity
Timeout
Number of seconds of inactivity before
TCP connection is closed
- 1000 R/W
Modbus
Production
List
The Production and consumption
Registers can be used to create custom
Modbus interface ranges. An example:
If field inputs register address 0 is put
into the first slot of the production
list, the field inputs register value will
be available in the first slot of the
Modbus Production Data Register range.
Production data is data provided by the
device and Consumption data is for data
provided (written) to the device. Note
that the values must be Modbus Register
Address (i.e., Register Number - 1) not
Register Number.
- 2000 R Modbus
Production
Data
-
- 3000 R/W
Modbus
Consumption
List
The Production and consumption
Registers can be used to create custom
Modbus interface ranges. An example:
If field inputs register address 0 is put
into the first slot of the production
list, the field inputs register value will
be available in the first slot of the
Modbus Production Data Register range.
Production data is data provided by the
device and Consumption data is for data
provided (written) to the device. Note
that the values must be Modbus Register
Address (i.e., Register Number - 1) not
Register Number.
- 4000 R/W
Modbus
Consumption
Data
-