Page 28
I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display
Help Message
Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
JAM OFF
4
Choose:
UL A ON
UL T ON
or
UL OFF
ENABLE UNDERLOAD ALARM
OR TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR
DISABLE
Toggles between
UL A ON, UL T
ON, and UL OFF
UL A ON
5
Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
UB A ON, UB T
ON, and UB OFF
UB A ON
6
Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
WD A ON, WD
T ON, and WD
OFF
WD A ON
7
Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
MB A ON, MB T
ON, and
MB OFF
MB A ON
8
Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING
ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
LB A ON, LB T
ON, and LB OFF
LB A ON
9
Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD
TEMP ALARM OR TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
AX A ON, AX T
ON, and AX OFF
AX A ON
10
Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME
TRIP OR ALARM TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
SX A ON, SX T
ON, and SX OFF
SX A
11
Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN
STARTS TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR
DISABLE
Toggles between
TBS T ON and
TBS OFF
TBS OFF
12
RTDF
ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD
CHANNEL FAILURE TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
RTDF ON and
RTDF OFF
RTDF ON
13
RCOM ON
or
RCOM
OFF
ENABLE RTD MODULE
COMMUNICATION FAILURE
TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
RCOM ON and
RCOM OFF
RCOM ON
14
IOCT ON
or
IOCT OFF
ENABLE INSTANTANEOUS
TRIP TO ACTIVATE ALARM
RELAY OUTPUT OR DISABLE
Toggles between
IOCT ON and
IOCT OFF
IOCT OFF
15
PH R ON
or
ENABLE PHASE REVERSAL
TRIP TO ACTIVATE ALARM
Toggles between
PH R ON and
PH R OFF
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...