I.L. 17562
Page 53
PR 0.3 Effective 8/99
5.3.3 Setpoint P3L3, Ground Fault Run Delay (GFRD) —
Sets the number of power cycles
that a ground fault trip or alarm operation must be maintained before the relay produces an
output.
5.3.4 Setpoint P3L4, Instantaneous Overcurrent Trip Level (IOC) —
Sets the instantaneous
overcurrent trip limit in percent of FLA above which the relay will trip. This trip type can be set to
OFF. For currents clearly above the setting, the IOC function picks up in two power cycles or
less. IOC operates only for high-current faults, and no run delay is needed. Use with IOC Start
Delay. Normally, set IOC above 1.5 times LRC. See Section 9.1.3.1.
The
IOC
setting must be below (1020 *
PCT
/
FLA
) or 1600%, whichever is less.
PCT
is Setpoint
P1L5;
FLA
is Setpoint P1L1. If this constraint is exceeded, you will not be able to exit program
mode, but will get a specific warning message instead.
5.3.5 Setpoint P3L5, Instantaneous Overcurrent Start Delay (IOCSD) —
Sets the number of
power cycles after a start is recognized until the instantaneous overcurrent trip and alarm
functions are enabled. Use this delay to inhibit IOC tripping on a current peak caused by
magnetic inrush when the motor is first energized - usually one to three cycles.
5.3.6 Setpoint P3L6, Jam Trip Level (JMT) —
Sets the motor jam current trip limit in percent of
FLA. This element can be set to OFF. Use with the jam start and run delays.
The jam trip function operates if the current rises well above FLA during running, perhaps due to
a mechanical jam in the load or a sudden larger-than-intended load. For example, see the jam
trip limits set at 180% of FLA in the upper RUN portions of protection curves of Figures 9.4 or
9.5.
The
JMT
setpoint must be below (1020 *
PCT
/
FLA
) or 1200%, whichever is less.
PCT
is
Setpoint P1L5;
FLA
is Setpoint P1L1. If this constraint is exceeded, you will not be able to exit
program mode, but will get a specific warning message instead.
5.3.7 Setpoint P3L7, Jam Start Delay (JMSD) —
Sets the number of seconds after a start is
recognized until the jam trip and alarm functions are enabled.
Use JMSD to block jam trips during starting. Use even longer values in high-inertia load
situations where the acceleration time is longer than the start time. In these cases, the motor
current may remain above FLA or JMT for some time after the transition from start to run.
5.3.8 Setpoint P3L8, Jam Trip Run Delay (JMTR) —
Sets the number of seconds that a jam
trip current level must be maintained before the trip output occurs.
Use JMTR to block undesired jam trips for temporary large loads which are normal for the
process - for example, a heavy load suddenly being placed on the conveyor belt which the motor
must accelerate.
5.3.9 Setpoint P3L9, Underload Trip Level (ULT) —
Sets the current level in percent of FLA
below which the MP-3000 determines that the motor has lost its load and trips the motor. This
element can be set to OFF. Use with the underload start and run delays.
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...