I.L. 17562
Page 29
PR 0.3 Effective 8/99
Line
No.
Display
Help Message
Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
PH R OFF
RELAY OUTPUT OR DISABLE
PH R OFF
16
INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE
SEQUENCE TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
INSQ ON and
INSQ OFF
INSQ OFF
17
REMT
ON
or
REMT
OFF
ENABLE REMOTE TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
REMT ON and
REMT OFF
REMT OFF
18
DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP
TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
DIFT ON and
DIFT OFF
DIFT OFF
19
INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
INCT ON and
INCT OFF
INCT OFF
20
TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP
TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
TRNT ON and
TRNT OFF
TRNT OFF
21
ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED
SWITCH TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR
DISABLE
Toggles between
ZSWT ON and
ZSWT OFF
ZSWT OFF
22
TBYP ON
or
TBYP OFF
ENABLE TRIP BYPASS TO
ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
TBYP ON and
TBYP OFF
TBYP OFF
Page 9 SP AUX1 SETPOINTS FOR AUX 1 RELAY OUTPUT CONFIGURATION
1
LSPU XXX
LOAD SHED PICK-UP
CURRENT AS % OF FLA
50-150%, OFF
(1% increments)
Note
: P9L1 and
P9L2 are forced
to be coherent.
See Section 5
explanation.
OFF
2
LSDO
XXX
LOAD SHED DROP-OUT
CURRENT AS % OF FLA
50-LSPU Value
%, OFF (1%
increments)
Note
: P9L1 and
P9L2 are forced
to be coherent.
See Section 5
explanation.
OFF
3
LSDL XX
LOAD SHED DELAY IN
SECONDS
0-5 sec. (0.1 sec.
increments)
1
If LSPU and
LSDO are both
set to OFF then
the SP AUX1
functions below
are available and
visible:
---
---
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...