I.L. 17562
Page 123
PR 0.3 Effective 8/99
Table 12.3 Troubleshooting: Operator Panel Malfunctioning
Symptom
Probable Cause
Solution
All LEDs and displays are off
or unintelligible.
Incoming ac deficient.
MP-3000 malfunctioning
The MP-3000 operates down
to 55% of rated voltage, but
such a low voltage isn't
normal and should be
diagnosed.
Verify that 120 or 240 Vac
(±15%) exists between
terminals 4 and 7.
Remove ac power completely
for 10 seconds and reapply. If
problem persists, return the
MP-3000 to the factory for
repair.
OPTO ERR message
Optocoupler failure trip based
on bad timing of ac input
waveform zero crossings.
Check the frequency setting
P1L7 for 50 or 60 Hz as
appropriate. Make sure 120
Vac is used for discrete inputs.
Energizing with dc will cause
this error message.
Metered current readings too
low or too high.
Incorrect current transformers
and/or PCT ratio setting P1L5.
Acceptable Ct ratio is dictated
by motor nameplate FLA.
PCT should be set to the
actual Ct ratio. See Ct
application advice in Section
5, paragraph 5.1.5.
Table 12.4 Internal Diagnostic Failure Messages
Display
Complete Help Message
A/D ERR
A/D CONVERTER ERROR TRIP
RAM ERR
RAM ERROR TRIP
ROM ERR
ROM ERROR TRIP
OPTO ERR
OPTOCOUPLER FAILURE TRIP
1
ZRAM ERR
NON VOLATILE MEMORY ELEMENT
SHOULD BE REPLACED
NOTES:
1. Refer to Table 12.3 for OPTO ERR.
2. Setpoint P12L16 lets the user choose whether these internal failures produce alarm plus trip,
or just an alarm.
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...