I.L. 17562
Page 121
PR 0.3 Effective 8/99
running speed.
•
Use DI 1 test to
confirm that the relay
sees the expected input
voltage.
REMOTE
REMOTE TRIP
Either or both of discrete
input 1 and/or discrete input
2 are set to indicate remote
trip contact input. The input
configured in this way was
energized with 120 Vac.
Determine the source of
the remote contact
operation requesting the
trip.
DIF TRIP
DIFFERENTIAL TRIP
Either or both of discrete
input 1 and/or discrete input
2 are set to indicate
differential trip contact input
from an external differential
relay. The input configured
in this way was energized
with 120 Vac.
DANGER.
Shut down
and lock out motor. A
differential relay
operation indicates an
electrical fault. Get
expert help in evaluating
condition of motor and
repair needs. Do not try
to restart without expert
evaluation.
After or during repair or
replacement of motor,
check fuses in starter
and replace blown fuses.
PH UNBAL
PHASE UNBALANCE
TRIP
•
Source voltage
unbalance due to
remote fault or single-
phase loading.
•
Single phasing of the
motor.
•
Check voltage
balance
•
Check integrity of
feeder connections.
•
Check fuses in starter.
•
Do not attempt restart
until cause of single-
phasing is found.
PH REVRS
PHASE REVERSAL
TRIP
At the time of starting, the
phase sequence was
reversed.
The MP-3000 is set for non-
reversing starter; the motor
is never supposed to run
backwards.
DANGER.
Careless
diagnosis and correction
could lead to starting the
motor in the wrong
direction. The cause is:
•
Incoming source has
swapped phases. Swap
two of the incoming
power leads L1, L2, or
L3 to correct.
•
Ct wiring has swapped
phases. Check wiring at
Ct and relay end.
Change the MP-3000
current transformer
wiring by swapping the
current transformer
wiring terminals H1B-
H2B with H1C-H2C.
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...