Page 106
I.L. 17562
PR 0.3 Effective 8/99
Section 10. DATA COMMUNICATIONS
10.1 General
Most MP-3000 setpoints and operating data can be viewed or changed on the front-panel
alphanumeric display. However, with the large volume of information and setpoints, many users
will find it more convenient to view or manipulate the data on a host computer with its large
graphic display.
The MP-3000 can communicate with Cutler-Hammer PowerNet
and previous-generation
IMPACC
distributed control systems or host software via the communications port and an
optional accessory PONI module mounted on or near the back of the relay.
In addition to monitoring and programming, PowerNet can execute control through
communications; including remote tripping, resetting, and emergency override.
One particular logging function, the starting current profile display, cannot be viewed on the relay
faceplate. The profile data must be uploaded to a PowerNet host computer after the start.
PowerNet provides an informative plot of the actual starting current curve, plotted along with the
cold-start protection limit curve, for checking of coordination. Profiles are saved for the last four
starts.
Older IMPACC systems do not directly support the MP-3000. However, the MP-3000 can be set
to emulate the communications of the older Cutler-Hammer or Westinghouse IQ 1000 II motor
relay.
10.2 Choosing a PONI -
The PONI (Product Operated Network Interface) module is
interchangeable among a number of available styles and provides the physical and electrical
interface to several communications links or networks. The MP-3000 can work with at least the
following PONI types:
•
I-PONI - INCOM Network PONI - the recommended means of connecting to the robust
INCOM communications network.
•
B-PONI - Buffered INCOM Network PONI - an older INCOM PONI type which can only be
used for communications in IQ 1000 II compatible mode. See Section 10.6 below.
•
RS232-PONI - RS-232 serial port PONI - for connecting to the serial port of a PowerNet host
computer or other serial device.
•
D-PONI - DeviceNet
PONI - a translating PONI for connection to a DeviceNet control
network. Check the firmware version of the D-PONI for compatibility with an IQ 1000 II or
an MP-3000.
•
E-PONI - Ethernet PONI, with 10BaseT or optical-fiber network connections - for direct
connection to a facility LAN which ties the MP-3000 to a PowerNet host client computer.
Contact a Cutler-Hammer sales engineer or the Power Management Products factory for
updated information on availability of PONI types.
Each type of PONI has its own instruction leaflet, with information on mounting and connection.
10.3 Mounting the PONI -
Attach the PONI to the back of the MP-3000 using the mounting
bracket supplied with the MP-3000. If the URTD module is to be mounted on the back of the
relay, mount the URTD module with its own bracket first; then attach the PONI to the back of the
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...