Clearly mark the new
wiring and update the
drawings for future
reference.
•
Check motor for
correct direction of
rotation at the moment
of starting.
T BYPASS
TRIP BYPASS
The MP-3000 tripped, yet
continued to see current
flowing to the motor for
more than a second after
the trip.
•
The contactor or
breaker is stuck or
jammed.
•
Or, someone has
bypassed the trip contact
so that the contactor
remained energized
after the trip.
•
Immediately open
upstream source breaker
or loadbreak switch.
Lock out this switch and
diagnose problem or find
bypass in starter.
INCOM
INCOM REMOTE TRIP
A remote PowerNet or other
data communications host
requested a motor trip.
Determine the cause of
the remote trip.
STEX MMM
STEX T
MAX NUMBER OF
STARTS PER TIME
REACHED,
REMAINING MINUTES
ACTIVE SHOWN
STARTS PER TIME
TRIP (log display only)
Too many starts were
performed in the user-set
period of time.
Wait for the oldest start
to clear from the stack.
Observe countdown on
display. See setpoints
P5L1 and P5L2.
TBS MMM
TIME BETWEEN
STARTS TRIP,
REMAINING MINUTES
ACTIVE SHOWN
Restarting blocked until
user-set time between starts
has expired.
Wait the indicated time
before restarting.
Note: The number of
cold starts (NOCS)
setpoint may suppress
this blocking during the
first n cold starts.
TRANSIT
LOW TO HIGH
VOLTAGE
TRANSITION ERROR
TRIP
Starting current was still
above the transition
threshold P5L5 when the
transition timer P5L6 delay
expired.
•
This trip is initiated
only if setpoint P5L7 is
set to TRN I or TRN
T/C. Check the
correctness of transition
settings.
•
Check motor and load
for a cause of slower
than expected
acceleration.
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...