Page 34
I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display
Help Message
Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
ALARM RELAY ENERGIZES
ON ALARM EVENT OR MODE
2 – ALARM RELAY
ENERGIZES ON POWER UP
AND DE-ENERGIZES ON
ALARM EVENT
AL MODE2
3
AX1 MOD
X
CONFIGURE AUX1 RELAY
OUTPUT TO BE MODE 1 –
AUX1 RELAY ENERGIZES ON
AUX1 EVENT OR MODE 2 –
AUX1 RELAY ENERGIZES ON
POWER UP AND DE-
ENERGIZES ON AUX1 EVENT
Toggles between
AX1 MOD1 and
AX1 MOD2
AX1 MOD1
4
AX2 MOD
X
CONFIGURE AUX2 RELAY
OUTPUT TO BE MODE 1 –
AUX2 RELAY ENERGIZES ON
AUX2 EVENT OR MODE 2 –
AUX2 RELAY ENERGIZES ON
POWER UP AND DE-
ENERGIZES ON AUX2 EVENT
Toggles between
AX2 MOD1 and
AX2 MOD2
AX2 MOD1
5
MAN I2T
or
AUTO I2T
AUTO OR MANUAL I2T
RESET
Toggles between
MAN I2T and
AUTO I2T
AUTO I2T
6
RUN PGM
or
STOP
PGM
ENABLES UNIT TO BE
PROGRAMMED WHILE
MOTOR IS RUNNING
Toggles between
RUN PGM and
STOP PGM
STOP
PGM
7
EMRG EN
Or
EMRG DIS
EMERGENCY OVERRIDE
ENABLE
EMRG EN – ENABLE
EMERGENCY OVERRIDE
EMRG DIS – DISABLE
EMERGENCY OVERRIDE
Toggles between
EMRG EN and
EMRG DIS
EMRG DIS
8
12 HOUR
or
24 HOUR
SET REAL TIME CLOCK
DISPLAY
12 HOUR – AM/PM TIME
DISPLAYED
13 24 HOUR – 24 HOUR
TIME DISPLAYED
Toggles between
12 HOUR and
24 HOUR
12 HOUR
9
MONTH XX
SET REAL TIME CLOCK
MONTH
Month 1-12 (1
month
increments)
-----
10
DAY XX
SET REAL TIME CLOCK DAY
Day 1-31 (1 day
increments)
-----
11
YEAR XX
SET REAL TIME CLOCK
YEAR
Year 0-99 (1
year increments)
-----
12
HOUR XX
SET REAL TIME CLOCK
HOUR
Hour 0-23 (1
hour increments)
-----
13
MIN XX
SET REAL TIME CLOCK
MINUTE
Minute 0-59 (1
minute
increments)
-----
14
M D Y
or
D M Y
SET REAL TIME DATE
DISPLAY
MONTH DAY YEAR OR
DAY MONTH YEAR
Toggles between
M D Y and D M
Y
M D Y
15
IQ2 EN
or
IMPACC COMMUNICATIONS
MODE
Toggles between
IQ2 EN and IQ2
IQ2 EN
Summary of Contents for 66D2032G01
Page 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Page 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Page 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Page 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Page 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Page 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Page 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Page 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Page 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Page 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Page 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Page 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Page 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Page 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Page 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Page 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...