Settings
32
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Active Mode
Description
Pull Coil
Cranking
section for more information.
LCD Backlight
Global
Active when LCD Backlight is active.
Voltage Regulator
Running
Active when engine is starting/running and is not in Idle Mode.
ETS (Energize to Stop)
ETS Timer
Active during Energize to Stop timer. See ETS On Duration under Timers >
for more details.
Off Mode (Not In Auto)
Off
Active when the controller is in the OFF mode.
Idle Mode
Idle Mode
Active when the controller is in IDLE mode. For example when the idle
switched input is active or during warmup and cooldown if warmup idle and
cooldown idle settings under Timers > Engine Logic are enabled.
Battle Mode
Battle Mode
Active when Battle Mode switched input is active.
System OK (System
Ready)
Auto, Run
Active when the controller is in the AUTO and RUN mode and no warnings
or failures are present.
Delay to Start
Delay to Start Timer
Active when the Delay to Start timer is active.
Glowplug
Preheat, Midheat,
Postheat
Active during the Preheat, Midheat and Postheat timers.
Warmup
Warmup Timer
Active in RUN mode after Warmup timer has expired. Is not active in the
cooling down state or other states. Typically used to apply load to engine
only after it has warmed up and to remove the load on cooldown.
Cooldown
Cooldown Timer
Active when Cooldown timer is active.
Engine Running
Running
Active after crank success.
Exercising
Exercise Timer
Active during the engine exercising cycle.
Batt. Recharge (Battery
Recharge)
Battery Recharge
Timer
Active during the battery recharge cycle.
Maintenance
(Maintenance Required)
Global
Active when Maintenance timer has expired. If the timer has expired when
the controller is in the RUN mode the output does not turn on until the
controller enters the OFF or AUTO mode. See the
LowBat InCrank (Low
Battery During Cranking)
Cranking
Active when Low Battery During Cranking warning is displayed.
Aux Sensor 1
Auxiliary Settings
Dependent
Active dependent upon settings in the
sensor section.
Aux Sensor 2
Aux Sensor 3
Aux Sensor 4
Force Regen
User Controlled
When user triggers a Force Regeneration, output is active for 20 seconds
then switches off.
Regen Inhibit
User Controlled
When user triggers a Regeneration Inhibit, output is active for 20 seconds
then switches off.
Common Failure
Any Failure
Active when any failure occurs.
RPM Increment
Running
Output is used to to trigger inputs on an ECM to control speed. See
RPM Decrement
Running
Output is used to to trigger inputs on an ECM to control speed. See
DEF Fluid Pump
Running
Active when DEF Fluid Level falls below the DEF Low Level and stays
active until the level rises above the DEF High Level. See
Genset Disable
Global
Disables the generator during a stationary Regen on Kubota engines (see
Aftertreatment in the J1939 User Manual ) or also during an engine IDLE
condition from the IDLE switched input. Automatic idle is ignored. If the
generator voltage is not below the under voltage setpoint in 10s, the
controller will shut down the engine on "Generator Disable Failure."
Dummy Load
Running
Output is controlled by the dummy load feature.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...