Installation
17
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
2.6.5
RelayPak (Optional)
Model Number: RP100-VM
The RelayPak is used to provide up to four built-in slave relays in a compact and easy to wire package. This allows the low
current outputs of the controller to switch on high current relays on the RelayPak.
Note:The relayPak can be used to sense DC voltages up to 39 VDC using one of the Auxiliary Sensor Inputs on the controller.
The VM in RP100-VM refers to this voltage sensing capability. Refer to drawing DWG1552 under www.dynagen.ca/support. If
this capability is used, the forth relay, Relay D, cannot be used.
Electrical Specifications
Specification
Rating
Operating Voltage
12V / 24V
Output Pilot Duty Rating
5.83A Per Relay @ 12V
Output Resistive Rating
10A Continuous Per Relay @ 12V
40A Momentary Per Relay @ 12V
Relay Style
Automotive Cube
Standards
UL 6200 recognized component. Consult
factory for UL conditions of acceptability.
WARNING
: You must use relays in the RelayPak that are suitable for the system voltage. Example: 12V relays in a
12V system and 24V relays in a 24V system.