Using the Controller
25
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
False
Restart
Warning
After going into the RUN mode the controller has determined the engine has not started after all and
will attempt to do another crank attempt. The fault restart feature under Engine Logic > Timers has to
be enabled.
Breaker
Tripped
Warning
The "Breaker Trip" switched output has been activated. This output is used to control the generator
breaker.
Over
Current
Warning
The generator AC current has risen above the Over Current warning setpoint under AC Monitor >
O.C. Protection > Basic Alarm.
Fuel In
Basin
Warning
The "fuel in basin" switched input has been triggered. This indicates there has been a leak in the fuel
tank.
Low
Battery
Warning
The main starter battery (the battery the controller is powered from) voltage has fallen below the low
battery warning setpoint under Sensors > Battery.
High
Battery
Warning
The main starter battery (the battery the controller is powered from) voltage has risen above the high
battery warning setpoint under Sensors > Battery.
Low Engine
Temp
Warning
The engine temperature has fallen below the low engine temperature warning setpoint set under
Sensors > Engine Temp. > Setpoints.
Battle
Running
Warning
The "Battle Mode" switched input has been triggered. The controller will not shutdown on any failures.
All failures will be ignored.
Under
Frequency
Warning
The generator AC frequency has fallen below the Under Frequency warning setpoint set under AC
Monitor > Genset Freq. > Setpoints.
Over
Frequency
Warning
The generator AC frequency has risen above the Over Frequency warning setpoint set under AC
Monitor > Genset Freq. > Setpoints.
Load
Imbalance
Warning
The generator load is imbalanced between the A, B, and C phases. This has to be enabled under AC
Monitor > O.C. Protection > Imbalance Mode.
Over
Voltage
Warning
The generator AC voltage has risen above the over voltage warning setpoint set under AC Monitor >
Genset Voltage. Possible issue with the voltage regulator or governing on the engine.
High Fuel
Temp
Warning
Doosan G2 electronic engine high fuel warning. This warning comes from the engine ECM over CAN
J1939.
Hi Exhaust
Temp
Warning
Doosan G2 electronic engine high turbine exhaust temperature. This warning comes from the engine
ECM over CAN J1939.
Failed To
Stop
Failure
The controller shut down the engine -- by turning off the Fuel output and (if enabled) by turning on the
Energize-To-Stop output -- but the engine speed did not go to zero after the energize to stop time
(under Timers > Engine Logic).
Breaker
Failed
Failure
The "Breaker Trip" switched output failed to turn off the breaker. This is triggered if the AC Current is
still above 10% of the rated current setpoint. The "breaker trip" failure has to be enabled under AC
Monitor > O.C. Protection > Brk Trip Fail.
Load
Imbalance
Failure
The generator load is imbalanced between the A, B, and C phases. This has to be enabled under AC
Monitor > O.C. Protection > Imbalance Mode with the mode set to ""Shutdown Trip".
Over
Current
Failure
The generator AC current has risen above the over current failure setpoint set under AC Monitor >
O.C. Protection > Basic Alarm.
ECM
Shutdown
Failure
Electronic engines only. CAN J1939 DM1 stop lamp is active; the ECM has shutdown the engine.
High
Engine
Temp
Failure
Engine temperature has risen above the high engine temperature failure setpoint set under Sensors
> Engine Temp.
Low Oil
Pressure
Failure
Engine oil pressure has fallen below the low oil pressure failure setpoint set under Sensors > Oil
Pressure.
Under
Speed
Failure
Engine speed has fallen below the under speed failure setpoint set under Sensors > Engine Speed.
Over
Speed
Failure
Engine speed has risen above the over speed failure setpoint set under Sensors > Engine Speed.
Low Fuel
Level
Failure
The fuel level has fallen below the low fuel level failure setpoint under Sensors > Fuel Level.
Low
Battery
Failure
The main starter battery (the battery the controller is powered from) voltage has fallen below the low
battery failure setpoint set under Sensors > Battery.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...