Settings
43
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Default
Description
1 ~ 6000
1
, 1 minute
increments
controller before turning off the output or shutting down the
controller.
If the Run Time is disabled then the start/output is held until the
Stop Level is reached (if enabled) or until the controller is reset or
powered down or, in the case of Start on Low / Start on High, until
the user presses the OFF button.
Note that the run time is not exact. Up to 10 seconds may be
added to the beginning of the run time counter and up to 4
seconds to the end. The run time begins when a start request is
received so crank time, preheat time, etc is included in the Run
Time.
Mode Settings >
Start Level
Disable
Temperature: 32 ~ 999,
1
0
F increments
Pressure: 1 ~ 6000, 1 psi
increments
Level: 1 ~ 99, 1 %
increments
Voltage: 0.1 ~99.9, 0.1 V
increments
Current: 1 ~ 999, 1 A
increments
-----
(Only applies if Func. Select is
not
set to Fault Monitor) The level
at which the auxiliary switched output turns on or the engine
starts.
If this is set to Disable, the Aux sensor action defined in Func.
Select is disabled. The Auxiliary sensor becomes display only
(unless Func. Select is set to Fault Monitor).
Mode Settings >
Stop Level
(Only applies if "Func. Select" is
not
set to Fault Monitor) The
level at which the auxiliary switched input turns off or the engine
is stopped.
If Stop Level is disabled the start/output condition is maintained
until the Run Time expires (if enabled) or until the controller is
reset or powered down or in the case of a start until the user
presses the OFF button.
Setpoints > Low
Warning
(Only applies if "Func. Select" is set to Fault Monitor) Reading at
which a warning occurs.
Setpoints > Low
Failure
(Only applies if "Func. Select" is set to Fault Monitor) Reading at
which a failure occurs.
Setpoints > High
Warning
(Only applies if "Func. Select" is set to Fault Monitor.) Reading at
which a warning occurs.
Setpoints > High
Failure
(Only applies if "Func. Select" is set to Fault Monitor.) Reading at
which a failure occurs.
Timers > Trigger Delays Aux Sensors menu:
Aux 1
1 to 3600 s, 1 s
increments
5 s
"Func. Select" set to fault monitor: Sets the amount of time to
ignore the input for warning and failure detection purposes. No
warnings or failures will be generated during this time.
"Func. Select" set to other than fault monitor: Sets the amount of
time to delay a start or stop event. If set to larger than 4 s the
stop delay portion is limited to 4 s. If the trigger for the start or
stop event becomes unavailable during this time the time will be
reset and the controller will wait for the next start/stop trigger.
Limitations: For TG350/TG410 firmware versions below 1.88.01
the maximum range is 45s.
Aux 2
Aux 3
Aux 4
1
1 ~ 600 minutes for firmware versions below 1.78.
If using
Output on Low
or
Output on High
one of the switched outputs events must be set to one of the following corresponding
to the Aux. Sensor being configured per the table below.
(Switched I/O > Switched Out A/B/C/D/EF > Events menus)
Name
Description
Aux Sensor 1
Used by the Aux. Sensor 1
Output On Low
or
Output on High
feature.
Aux Sensor 2
Used by the Aux. Sensor 2
Output On Low
or
Output on High
feature.
Aux Sensor 3
Used by the Aux. Sensor 3
Output On Low
or
Output on High
feature.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...