Settings
57
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
NOTE
: The maintenance timer displays "Service Required" when this time expires. This message is only displayed the next
time the controller enters the RUN mode. If the timer expires when the controller is in the RUN mode the message is not
displayed.
4.6
AC Monitor
The controller has the ability to monitor AC voltage from a generator. The following sections are used to configure settings
associated with AC monitoring.
4.6.1
Generator Voltage
The following settings are used to configure the controller's response to voltage measurements.
(AC Monitor > Genset Voltage menu)
Name
Range
Default
Description
Voltage
Source
Disable
2-Wire Single
3-Wire Single
3-Wire 3-Phase
4-Wire 3-Phase
4-Wire Delta
Auto Selection
3-Wire
Single
The wiring configuration of the generator. Disable will disable AC
voltage and AC frequency sensing and display.
2-Wire Single: One 120VAC L-N. Use phase A.
3-Wire Single: 120/240VAC systems. Use phases A and B.
3-Wire 3-Phase: Three phase delta without a ground.
4-Wire 3-Phase: Three phase Wye system. Center taped ground.
4-Wire Delta: Delta with a ground. The high leg is phase B. For
example if A-N and C-N read 120VAC then B-N will read 208VAC.
Selecting Auto Selection will use the
determine the wiring configuration.
Scaling Factor 0.500 ~ 2.500 in
0.001 increments
1.000
The gain to apply to the AC voltage that is read at the controller. See
below for more information.
Nominal Volts
50 ~ 800 VAC* in 1
VAC increments
240 VAC
Generator line-to-line voltage output when operating under normal
running conditions.
Auto Nominal
> 1Ph 3-Wire
(1-Phase 3-
Wire)
50 ~ 800 VAC* in 1
VAC increments
240 VAC
inputs.
Auto Nominal
> 3-Phase (1)
50 ~ 800 VAC* in 1
VAC increments
208 VAC
Auto Nominal
> 3-Phase (2)
50 ~ 800 VAC* in 1
VAC increments
480 VAC
Auto Nominal
> 3-Phase (3)
50 ~ 800 VAC* in 1
VAC increments
600 VAC
Auto Scaling >
1Ph 3-Wire (1-
Phase 3-Wire)
0.500 ~ 2.500 in
0.001 increments
1.000
Scaling Factor when using the
Auto Scaling >
3-Phase (1)
0.500 ~ 2.500 in
0.001 increments
1.000
Auto Scaling >
3-Phase (2)
0.500 ~ 2.500 in
0.001 increments
1.000
Auto Scaling >
3-Phase (3)
0.500 ~ 2.500 in
0.001 increments
1.000
Auto Single
A-C Phase
A-B Phase
A-B Phase
For 1-Phase 3-Wire when using the
determines which phases the single phase voltage is read from.
Setpoints >
Low Warn
50 ~ 99 % in 1 %
increments
90 %
Reading at which a warning occurs.
Setpoints >
Low Fail
50 ~ 99 % in 1 %
increments
85 %
Reading at which a failure occurs.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...