Settings
38
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Default
Description
Setpoints > High Fail
(Over Speed Failure)
101 ~ 150%
115 %
A over speed failure is triggered if the speed is above this threshold for
4 seconds.
RPM Control > Min
Speed
500 ~ 4000 rpm
in 1 rpm
increments
600 rpm
Front Panel Speed Control SettingsSee
section for more information on these settings.
RPM Control > Max
Speed
500 ~ 4000 rpm
in 1 rpm
increments
2000
rpm
RPM Control > Speed
Bias
0 to 600 rpm in
1 rpm
increments
30 rpm
RPM Control > Tsc1
RPM/s
Disabled, 10 to
300 rpm in 10
RPM increments
200 rpm
RPM Display
Blank
AC Hertz
Aux Sensor 1
Aux Sensor 2
AC
Hertz
RPM Switch >
Secondary (Secondary
RPM / 50Hz)
500 ~ 4000 rpm
in 1 rpm
increments
1500
rpm
The Rated RPM when the Secondary RPM / 50Hz is selected. See
RPM Switch > Primary
(Primary RPM / 60Hz)
500 ~ 4000 rpm,
1 rpm
increments
1800
rpm
The Rated RPM when the Primary RPM / 60Hz is selected. See
RPM Output
See the the
NOTE
: When using J1939 or Genset Voltage as a signal source, connections to the speed sensing terminals are
not required.
IMPORTANT
: When using Genset Voltage as a signal source the voltage source must be connected to terminal A
(J7-1). AC frequency is sensed on terminal A only.
NOTE
: Speed is monitored at the start of cranking. If there is speed detected above the crank disconnect setting
then cranking and idle is skipped.
The speed is not monitored during delay-to-start or preheat as this provides some degree of protection against
spurious signals due to noise. The fuel input is turned on at the start of preheat and often powers external
equipment that can cause noise.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...