Settings
40
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
When the controller is running and there are other functions occurring, the controller will scroll through its display parameters as
usual. When the speed control page is displayed, it will show the Engine Speed as well as the following instructions: Hold
AUTO + Up/Down to Adjust RPM.
Speed Control Parameter Page
Speed Control Adjust Page
Pressing and holding the AUTO button will display the screen to the right. If a 'Display Adjust Parameter' is set, it will also be
displayed underneath the Engine Speed. While still holding the AUTO key, press the up or down arrows to adjust the RPM. The
Engine Speed display should update as the engine physically changes its speed to accommodate the speed request.
NOTE
: When using switched outputs for speed control, the Set RPM will display '---' instead of the set speed.
4.4.4.2 RPM Output
This feature can be used to turn an output on and off when the speed of the engine/generator rises or falls below a given
speed.
To use this feature a
has to be set to "Rpm Output".
(Sensors > Engine Speed)
Name
Range
Default
Description
RPM Output
SubMenu
-----
-----
RPM Output >
Debounce
0.2 s to 10 s, 0.2 s
increment
2 s
Sets the time to wait before turning on or off the
switched output.
RPM Output > Trigger Disable, Under, Over
Disable
Sets when to turn on the switched output relative to
the Switched RPM setting.
RPM Output > Switch
RPM
500 to 3000 rpm, 1 rpm
increments
1800 rpm
Sets the RPM to trigger on. Trigger is based off of
this setting.
4.4.5
Battery
Use the following settings' configurations to allow the controller to read and interpret the battery voltage level.
Name
Range
Default
Description
Battery
Recharge
Enable ~
Disable
Disable
Enables or disables the ability to have the engine start on low battery voltage in
order to charge it.
Recharge Setup
-> Level
6.0 - 30.0V
10.4 V
Voltage level at which the controller starts the engine to recharge the battery.
Recharge Setup
-> Pre-Alarm
1 ~ 30
minutes
5 min
Amount of time to display a warning before starting the engine.
Recharge Setup
-> Duration
10 ~ 900
minutes
90 min
Amount of time to run the engine.
Setpoints ->
Low Warning
Disabled, 6.0
~ 24.0V
11.3 V
Reading at which a warning occurs.
Setpoints ->
Low Failure
Disabled, 6.0
~ 24.0V
Disabled
Reading at which a failure occurs.
Setpoints ->
High Warning
Disabled,
12.0 ~ 32.0V
Disabled
Reading at which a warning occurs.
Setpoints ->
High Failure
Disabled,
12.0 ~ 32.0V
Disabled
Reading at which a failure occurs.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...