Settings
44
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Aux Sensor 4
Used by the Aux. Sensor 4
Output On Low
or
Output on High
feature.
The display resolution of the auxiliary sensors that are displayed on the screen are different than the resolution used for the
purpose of the comparisons that determine if the start level, stop level, low warning, etc are in effect. The resolutions are given
below.
Sensor Unit Type
Comparison Resolution
Temperature
1
0
F
Pressure
1 psi
Level
1 %
Voltage
0.1 V
Current
1 A
Example: if the auxiliary sensor 1 (aux 1) is using a temperature sender curve, set to Output on Low, and the Start Level is set
to 130
0
F then the Output will not turn on until the temperature drops to 129
0
F since the resolution for comparisons is 1
0
F.
The below tables gives all the possible actions that the auxiliary sensors can perform.
Behavior
Func.
Select
Start Level
Run Time
Stop Level
A -
Indefinitel
y
Start controller when the sensor
drops below a certain value. Run
indefinitely.
1
Start on
Low
Set to value that the
sensor needs to
drop below to start.
Disable
Disable
Turn on an output when the
sensor drops below a certain
value. Keep on the output
indefinitely.
2
Output on
Low
Set to value that the
sensor needs to
drop below to turn on
the output.
Disable
Disable
Start controller when the sensor
rises above a certain value. Run
indefinitely.
1
Start on
High
Set to value that the
sensor needs to rise
above to start.
Disable
Disable
Turn on an output when the
sensor rises above a certain
value. Keep the output on
indefinitely.
2
Output on
High
Set to value that the
sensor needs to rise
above to turn on the
output.
Disable
Disable
B - Fixed
Duration
Start controller when the sensor
drops below a certain value. Run
for a fixed period of time and then
stop controller.
Start on
Low
Set to value that the
sensor needs to
drop below to start.
Set to the desired run
duration.
Disable
Turn on an output when the
sensor drops below a certain
value. Run for a fixed period of
time and then turn off the output.
Output on
Low
Set to value that the
sensor needs to
drop below to turn on
the output.
Set to the desired
duration to keep the
output on.
Disable
Start controller when the sensor
rises above a certain value. Run
for a fixed period of time and then
stop controller.
Start on
High
Set to value that the
sensor needs to rise
above to start.
Set to the desired run
duration.
Disable
Turn on an output when the
sensor rises above a certain
value. Run for a fixed period of
time and then turn off the output.
Output on
High
Set to value that the
sensor needs to rise
above to turn on the
output.
Set to the desired
duration to keep the
output on.
Disable
C - Start
Level /
Stop
Level
Start controller when the sensor
drops below a certain value. Stop
controller when the sensor rises
above a certain value.
Start on
Low
Set to value that the
sensor needs to
drop below to start.
Disable
Set to the value
the sensor needs
to rise above to
stop the
controller.
Turn on an output when the
sensor drops below a certain
value. Turn off output when the
sensor rises above a certain
value.
Output on
Low
Set to value that the
sensor needs to
drop below to turn on
the output.
Disable
Set to the value
the sensor needs
to rise above to
turn off the output.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...