Settings
56
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.5.2.2 Weekly Scheduler
The weekly scheduler allows up to 16 unique weekly exercise times to be created. By default all schedulers are disabled.
Timers > Week Scheduler:
Name
Range
Description
Weekday
Sunday ~ Saturday
The day of the week the exercise will take place on.
Start time
24 hour clock in 1
minute increments
When the exercise should start on a give day. At the
selected time a one minute prealarm is displayed on the LCD
screen. The controller starts after this one minute period.
Run time
10 ~ 1440 min in 1 min
increments
The duration of the exercise run period. Up to one day.
When entering the Week Scheduler menu there will be 16 sub menu items each corresponding to one of the 16 weekly
exercise times. If disabled the entry will have dashed lines: "--- --:-- -----". If enabled the day of week, start time, and duration
will be displayed for the menu. Press enter will enter the sub menu for that exerciser time.
It is recommended to use the RapidCore Configuration Software to enter the times as this provides a much more convenient
interface especially if daily exercise times are wanted.
4.5.2.3 Long Time Run
The Long Time Run counter can be used to shutdown the controller after a very long period of time. This is useful for remote
primary power applications where the user wants to divide run time between two generators. When the countdown expires the
controller will shutdown. Long Time Run is only active if the generator was started manually (i.e. by pressing the front Run
button).
Timers > Long Time Run:
Name
Range
Default
Description
Start Trigger
Disable or Manual Start
Disable Set to "Manual Start" to enable the Long Time Run feature.
Run Duration
1 ~ 5000 hours in 1 hour
increment
1 hour
The amount of time to run before shutting down.
4.5.3
Maintenance
The controller has the ability to count down the time between scheduled maintenance events. Once maintenance is required,
the controller will alert the operator via the LCD screen and a switched output (if enabled) wired to a lamp / horn / buzzer. The
following settings are used to configure the maintenance timer.
(Timers > Maintenance)
Name
Range
Default
Description
Reset
Counter
Yes or No
-----
Once the maintenance count interval expires, use this to reset the time and turn
off the switched output (if enabled). Select Yes to reset the counter and exit the
menu. Select No to exit the menu without resetting the counter.
Enable
Counter
Enable or
Disable
Disable
Enables or disables the maintenance function.
Count
Interval
10 ~ 9990
hours in 5
hour
increments
1000 hours
Determines the number of hours between required maintenance. A switched
output can be configured to turn on once the count interval expires.
To determine the amount of time until the next scheduled maintenance, follow these menu steps:
Main Menu -> Device Info. -> Maintenance
Maintenance counter is disabled if '----' is displayed. A negative number indicates the amount of time since maintenance timer
expired.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...