![Dycor SmartVue Process Control Monitor Operator'S Manual Download Page 94](http://html.mh-extra.com/html/dycor/smartvue-process-control-monitor/smartvue-process-control-monitor_operators-manual_2545949094.webp)
SmartVue Operator’s Manual
84
10-0004-R13
Refer to Appendix 0 for the complete list of Modbus Input Registers that are available for
reading SPN data.
When reading the DTC data, up to 16 separate ECUs can be simultaneously monitored.
With each ECU, access to its status, lamp state, and the number of codes that have been
produced is available. Up to 10 DTCs along with their related FMI (Fault Mode
Identifier) and OC (Occurrence Count) information can be accessed for each ECU.
The table below shows the registers and accompanying data for the first ECU followed
by two sets of DTC data (four registers each). Refer to Appendix 21.4.6 for a more
complete table.
Table 12-1 DTC Modbus register mapping
Address
Register ID
Modicon
Modicon
Data
1100
1101
31101
41101
STATUS1
ECU1
1101
1102
31102
41102
ECU1
1102
1103
31103
41103
LAMP1
1103
1104
31104
41104
NCODES1
DTC1
1104
1105
31105
41105
DTC1-1_H
1105
1106
31106
41106
DTC1-1_L
1106
1107
31107
41107
FMI1-1
1107
1108
31108
41108
OC1-1
DTC2
1108
1109
31109
41109
DTC1-2_H
1109
1110
31110
41110
DTC1-2_L
1110
1111
31111
41111
FMI1-2
1111
1112
31112
41112
OC1-2
…
…
…
…
…
12.4 User Registers
The SmartVue has a set of Modbus registers that can be written to during Modbus
communication called user registers. These are the only Modbus registers can be used as
the inputs to a process or control. There are 8 of each data type and there are 5 data
types. The data types are:
16-bit unsigned integer
16-bit signed integer
32-bit unsigned integer
32-bit signed integer
32-bit float
There is a separate screen for each data type and each screen displays the real-time
current value and the number of seconds since the value was last updated. The seconds
since update can be used in a process or control to optionally use a different value if the
updates have stopped. Two of the User Register screens are shown below.