28

4.2 Shutdown Conditions

Under various entrapment conditions the operator will assume either a 

soft

 or 

hard (alarm)

 shutdown. To determine what 

type of reset action is required, you will need to understand how the different entrapment conditions affect the gate operator.

This occurs in various situations where the inherent or secondary entrapment protection devices have been activated. In a soft 
shutdown condition, the operator 

will not

 respond to any input that was present when the entrapment protection device sensed an 

obstruction. If the gate stops at the open position, the operator will not respond to the automatic close timer.

Note: In some systems, the time clock input comes from the telephone entry system relay. This same relay may also provide open 
commands for a card reader, MicroPLUS transmitters and the visitor telephone entry. If so, these devices will also be disabled in a 
soft shutdown condition.

Note: The audio alarm will remain activated for a maximum of five minutes, or until the operator receives a reset input. The hard 
shutdown condition will remain in affect even if the audio alarm shuts off after five minutes.

In some conditions, a soft shutdown will reset as soon as the entrapment condition clears. For example, if a non-contact sensor 
(photo cell) is sensing an obstruction, the operator will stop the gate and assume a soft shutdown condition. When the photocell 
clears, the operator will return to normal operation. 

When the operator is in a soft shutdown, activation of any “intended input” will reset the operator. An “ intended input” includes 
any command, any standard safety input and any loop input. Activating any of these inputs will reset the gate. At that point the 
gate will return to normal operation. If the gate is open, the automatic close timer will then time out and close the gate.

 

Example 1

 - A time clock keys the gate open in the morning and an entrapment protection device senses an 

  obstruction prior to the gate reaching the full open position. If the entrapment is sensed by the inherent system, the 
  gate will reverse and run back to the closed position. The time clock input is still present, but the gate will not re-open.

 

Example 2

 - If the gate is closing and an entrapment protection device is activated, the gate will either stop or reverse 

  and run back to the open position, depending upon if the secondary or inherent device was activated. The automatic 
  close timer will not close the gate.

 

Example 3

 - Vehicle arrives at exit loop and gate runs towards the open position. If the inherent entrapment protection 

  gets activated during this opening cycle, the gate reverses and runs back to the closed position. After the inherent 
  entrapment protection is cleared, If the vehicle is still present at the exit loop, a soft shutdown condition does not 
  occur. The exit loop input provides an immediate reset of the operator and the gate will again run to the open position.

 

Example

 - The gate is closing and the inherent entrapment protection system senses an obstruction and causes the 

  gate to reverse direction. As the gate begins to run in the open direction, a second obstruction is sensed prior to the 
  gate reaching the full open position. Once the second obstruction has been sensed, the operator will stop, the audio 
  alarm will be activated and all standard inputs are shut down (including open commands, safety commands, loop 
 inputs, 

etc.).

  After 5 minutes, the audio alarm will “chirp” every 5 seconds. This indicates that the operator is in a hard shutdown 

  condition and the reset button must be pressed to reset the operator and silence the alarm.

Soft Shutdown

Resetting a Soft Shutdown

A hard shutdown condition occurs when the inherent entrapment protection system has sensed 

TWO consecutive obstructions 

before the gate reaches the full open or closed position.

Hard Shutdown (Alarm Activated)

Note: DoorKing operators have a built-in alarm reset push button mounted on the operator. Activating this button will return the 
gate operator to normal operation, but will not cycle the gate operator.

The operator is in a hard shutdown condition when the audio alarm is activated or audio alarm “chirps” every 5 seconds). To 
reset the gate operator and return it to normal operation, push the alarm reset button. A remote alarm/reset station (P/N 
1404-080) can be mounted external of the gate operator provided that it is installed in the line-of-sight of the gate and gate 
operator.

Once the gate has been reset, an open or close command is needed to start the gate operator. Most activating commands will 
cause the gate operator to cycle to the open position. This includes activation of a key switch or open command and activation of 
an automatic exit loop. Activation of a close command will run the gate to the closed position.

  Before resetting a hard shutdown, determine why the shutdown occurred. Inspect the gate for any obstructions along 

  its path that could have activated the inherent entrapment sensing system. Inspect the gate and gate hardware.

Resetting a Hard Shutdown

Summary of Contents for Series 9500

Page 1: ...t ions SE RIO US INJ UR Y OR DE AT H WARNING MOVING GATE CAN CAUSE Operate gate only when gate area is in sight and free of people and obstructions Do not allow children to play in gate area or operat...

Page 2: ......

Page 3: ...ided Gear Ratio Traveling Speed Amp Horsepower Voltage Phase Max Gate Weight Installed Level Max Gate Length Installed Level Brake Use this manual for the 9500 series operators with circuit board 4404...

Page 4: ...0 10 10 11 12 13 13 14 14 15 16 17 18 19 20 1 1 Gate Hardware 1 2 Removing Cover 1 3 Underground Conduit Requirements 1 4 Concrete Pad Description 1 5 Mounting Operator and Chain 1 6 Installation of C...

Page 5: ...lt In Controls and Reset Buttons Description 4 2 Shutdown Conditions Soft Shutdown Hard Shutdown 4 3 Manual Gate Operation 5 1 Maintenance 5 2 Built In Diagnostic Tests 5 3 Troubleshooting 5 4 Accesso...

Page 6: ...parate access opening The pedestrian access opening shall be designed to promote pedestrian usage Locate the gate such that persons will not come in contact with the vehicular gate during the entire p...

Page 7: ...talled used and maintained serious injuries or death can result Be sure that the installer has instructed you on the proper operation of the gate and gate operator system Be sure that the installer ha...

Page 8: ...eral public in which unauthorized access is prevented via supervision by security personnel This table illustrates the entrapment protection requirements for each of the four UL325 classes A Inherent...

Page 9: ...intended for vehicular traffic flow at entrances or exits to areas such as parking garages lots or toll areas VEHICULAR HORIZONTAL SLIDE GATE OPERATOR OR SYSTEM A vehicular gate operator or system th...

Page 10: ...ge A gap measured in the horizontal plane parallel to the roadway between a fixed stationary object nearest the roadway such as a gate support post and the gate frame when the gate is in either the fu...

Page 11: ...e potential of the gate closing on vehicular or other traffic that loops cannot sense Installed on the fence to help minimize the potential of entrapment between the gate and fence A filler post or ba...

Page 12: ...r High Voltage Power Sweeps Concrete Pad Concrete Pad 3 4 Inch Minimum Primary Operator Position Secondary Operator Position SECTION 1 INSTALLATION Prior to beginning the installation of the slide gat...

Page 13: ...View End View Front View Back Anchor Foot Front Anchor Foot Concrete Pad Conduit Area Front Anchor Foot Front Anchor Foot Back Anchor Foot Above Ground Re bar Re bar Re bar Sleeve Anchors Note Minimu...

Page 14: ...to gate Chain brackets MUST be mounted so the chain remains the same height as it is on the idler wheels Connect Chain to Chain Bracket Positioning Operator and Chain Brackets Attach Operator to Concr...

Page 15: ...or longer gates to support the weight of the chain DoorKing offers a chain tray and supporting brackets in sections to fit any length gate DoorKing P N 2601 270 10 Ft section Supporting Bracket Suppor...

Page 16: ...re attempting to connect any wiring to the operator be sure that the circuit breaker in the electrical panel is in the OFF position Permanent wiring must be installed to the operator as required by lo...

Page 17: ...setting See page 24 for limit nut descriptions 2 Operation of relay is dependent on setting of SW 1 switches 4 and 5 See page 22 for DIP switch function descriptions Relay contacts can be set for Nor...

Page 18: ...sing edge sensor has been activated and the gate is traveling to the close position but the close reversing edge sensor gets activated the gate will stop and enter a soft shutdown condition 4 Close Ed...

Page 19: ...ens gate Important Controls must be far enough from the gate so that the user is prevented from coming in contact with the gate while operating the controls Outdoor or easily accessible controls shoul...

Page 20: ...Engaged 2 6 Auxiliary Device Wiring Gate Tracker DoorKing Access Control System Model 1833 1835 1837 or 1838 tracker system can be connected This system can keep track of gate operator cycle count sho...

Page 21: ...les without having to use a transmitter or keypad The exit loop can be placed 20 100 feet away from the gate so the gate has started opening or has completely opened by the time you drive up to it Rev...

Page 22: ...ugh path while gate is moving Read owner s manual and safety instructions SERIOUS INJURY OR DEATH Secondary Entrapment Protection Devices Secondary Operator Primary Operator To Close Photo 2 To Open E...

Page 23: ...cuit board to the desired setting See switch setting charts on next 2 pages DIP Switches SW 2 is Upside Down on Board SW 1 is Upside Down on Board LEDs Indicates that low voltage power is applied to t...

Page 24: ...to close gate Auto close timer is ON Adjustable from 1 23 seconds to close gate Self Test Gate Opens Uphill 3 Gate Opens Downhill 6 Relay activates and LED is ON when the gate is fully open Relay act...

Page 25: ...he board will be activated This relay can be used as a switch for various functions such as illuminating a warning light when the gate is moving or turning on a green light when the gate is full open...

Page 26: ...ts After adjusting the limit nuts be sure that the lock plate is engaged in the slots on the limit nuts to prevent them from rotating The slow down limit assembly will move up or down 3 4 inch DO NOT...

Page 27: ...tandards The gate will reverse direction upon encountering an obstruc tion in either the opening or closing gate cycle For the reverse system to function correctly the gate must be properly installed...

Page 28: ...e gate speed The digital readout on the speed controller will display the gate speed The 10 1 gear reducer 9500 models are equipped with a speed brake It is automatically controlled by the speed contr...

Page 29: ...repairs to gate hardware 7 The entrance is for vehicles only Pedestrians must use separate entrance 8 SAVE THESE INSTRUCTIONS Unlock If padlocked and remove the cover See section 1 2 Removing cover on...

Page 30: ...ed The automatic close timer will not close the gate Example 3 Vehicle arrives at exit loop and gate runs towards the open position If the inherent entrapment protection gets activated during this ope...

Page 31: ...catch 3 Lift cover off vertical BE CAREFUL not to hit internal components with cover Idler Wheels Padlock Not Provided 1 2 3 Manually Crank Remove the Cover 1 2 Insert the supplied manual hand crank i...

Page 32: ...ould they become entrapped in the gate When servicing this gate operator always turn power OFF Operator Component Maintenance Monthly Interval 6 3 12 Alarm Chain Fire Dept Gate Loop s Release Primary...

Page 33: ...there are no shorted or open control wires from the keying devices to the gate operator If a keying device fails to open the gate press the Key Switch or momentarily jumper across terminals 1 and 5 on...

Page 34: ...ate operator and check that the gate slides freely without any binding Check the loop detector LEDs and input LEDs Any that flash ON will cause the gate to reverse Replace the circuit board Operator h...

Page 35: ...e integrity of ground loops P N 9401 045 3 Button Control Station Provides open close stop manual operation of the gate Stand Alone Box P N 1200 006 Interior fits in single gang box P N 1200 007 Inter...

Page 36: ...enue Inglewood California 90301 U S A Phone 310 645 0023 Fax 310 641 1586 www doorking com Owner s Manual Series 9500 Series 9500 Maximum Security Heavy Duty Vehicular Slide Gate Operators 9510 065 D...

Reviews: