61
B.4 PC1616/PC1832/PC1864 and PC5700 Fire Module Communications Connections
For ULC Listed Fire Monitord Installations
B.5 Sensor Reset for 2-Wire Smoke Detectors
AUX Connection
B.6 Sensor Reset for 4-wire Smoke Detectors
AUX Connection
B.7 Other PGM Connections
To L o c a l
P h o n e s
To L o c a l
P h o n e s
12V 4.0Ah/7Ah
12V 7Ah
22
0
2-WIRE SMOKE DETECTORS
AUX
YEL
GRN
BLK
RED
+
2200
END-OF-LINE
RESISTOR
EOLR-3
Ω
(+)
(-)
+ BELL -1 PGM 2
Compatiblity Identifier: PC5-2
Maximum Operating Voltage: 13.75VDC
Maximum Circuit Resistance: 100
(total)
mix different models on the
same circuit as correct operation
may be impaired.
Ω
Do not
Refer to the 2-wire smoke detector compatibility chart in this manual
NOTE:
Do not combine the 2-wire smoke detector and 4-wire
smoke detector on PGM2 (only 2-wire smoke detectors on
PGM2).
SMOKE
DETECTOR
POWER
12 VDC
IN
OUT
NO
ALM
-
OUT
+
-
IN
+
BLK
WHT
RED
GRN
LATCHING 4-WIRE
SMOKE DETECTOR
FOR EXAMPLE,
DSC MN240 Series.
EOLR-2
END OF LINE RESISTOR
5600
0.5W
Ω
Refer to installation guidelines in
Installation Manual and detector manufacturer's
literature when locating smoke detectors.
RM-1 POWER LOOP
SUPERVISORY RELAY
12V
DC 35mA MAXIMUM
WHT
4-WIRE SMOKE DETECTORS
Smoke Detector must be latching type (such as
DSC MN240 Series).
To reset smoke detectors, enter [ ] [7] [2].
✱
+ AUX
PGM 2
1
Zone
Input
COM
ALARM
INITIATING
LOOP
RESISTANCE:
100
Ω
PGM1
PGM2
PGM3
PGM4
PGM1 PGM2 PGM3 PGM4
NOTE:
For devices requiring more than 50mA, use a relay (DSC RM-1)
or UL-recognized parts only for this application.
NOTE:
The RM-1 relay module cannot be installed outside of the main
panel enclosure.