5
The following section provides a description of how to wire and configure devices and zones.
2.1 Installation Steps
The following steps are provided to assist with the installa-
tion of the panel. It is suggested that you read over this sec-
tion briefly to get an overall understanding of the order of
installation. Once this is done carefully work through each
step. Working from this plan will help reduce problems and
reduce the overall installation time required.
Step 1 Create a Layout
Draw a rough sketch of the building and include all alarm
detection devices, zone expanders, keypads and all other
modules that are required.
Step 2 Mounting the Panel
Locate the panel in a dry area, preferably located near an
unswitched AC power source and the incoming telephone
line. Before attaching the cabinet to the wall be sure to press
the five circuit board mounting studs into the cabinet from the
back.
NOTE:
Complete all wiring before applying AC or connect-
ing the battery.
Step 3 Wiring the Keybus
Wire the Keybus to each of the modules following the guide-
lines provided in Section 2.4.
Step 4 Assigning Zones to Zone Expanders
If zone expander modules are being used the modules must
be configured so the panel knows which zones are assigned
to each expander. Follow the guideline provided in Section
2.6 to assign zones to expanders.
Step 5 Zone Wiring
Power down the control panel and complete all zone wiring.
Follow the guidelines provided in section 2.10 to connect
zones using normally closed loops, single EOL resistor, dou-
ble EOL resistors, Fire zones and Keyswitch Arming zones.
Step 6 Completing Wiring
Complete all other wiring including bells or sirens, telephone
line connections, ground connections or any other wiring
necessary. Follow the guidelines provided in section 2.2 “Ter-
minal Descriptions”.
Step 7 Power up the Control Panel
Once all zone and Keybus wiring is complete, power up the
control panel.
NOTE:
The panel will not power up if only the battery is con-
nected.
Step 8 Keypad Assignment
Keypads must be assigned to different slots to be properly
supervised. Follow the guideline provided in section 2.7 to
assign keypads.
Step 9 Confirming Module Supervision
By default, all modules are supervised upon installation.
Supervision is enabled at all times so that the panel can indi-
cate a trouble if a module is removed from the system.
To confirm that each module is properly supervised, follow
the guidelines provided in section 2.8.
Step 10 Programming the System
Section 4.0 provides a complete description of how to pro-
gram the panel. Section 5.0 contains complete descriptions
of the various programmable features, what options are
available and how the options function. The Programming
Worksheets should be filled out completely before attempt-
ing to program the system.
Step 11 Testing the System
Test the panel completely to ensure that all features and
functions are operating as programmed.
2.2 Terminal Descriptions
AC Power Terminals
The panel requires a 16.5V, 40VA transformer. Connect the
transformer to these terminals.
The panel can be programmed to accept a power line fre-
quency of either 50Hz AC or 60Hz AC in programming sec-
tion [701], option [1].
NOTE:
Do not connect the transformer until all other wiring
is complete
.
Battery Connection
The battery is used to provide back up power in the event of
an AC power failure and to provide additional current when
the panel demands exceed the power output of the trans-
former, such as when the panel is in alarm.
NOTE:
Do not connect the battery until all other wiring is
complete
.
Connect the RED battery lead to the positive of the battery,
the BLACK battery lead to the negative.
The High Current Charge/Standard Battery Charge
option (section [701], option [7]) allows you to choose
between a high current battery charge and the standard bat-
tery charge rate.
High Current/Standard Battery Charge . . . . . . . . .Section [701]: [7]
Auxiliary Power Terminals - AUX+ and GND
These terminals provide up to 500mA of current at 12 V
DC
(700mA of current at 12V
DC
for UL/ULC) (550mA of current
at 12V
DC
for IMQ) for devices requiring power (rated 11.6-
12.6 V
DC
for UL residential applications). Connect the
positive side of any device requiring power to the AUX+ ter-
minal, the negative side to GND. The AUX output is pro-
tected; if too much current is drawn from these terminals
(wiring short) the panel will temporarily shut off the output,
until the problem is corrected.
NOTE:
When using a 12V 14Ah battery, the maximum AUX
capacity for 24-hour standby is 470mA.
Bell Output Terminals - BELL+ and BELL-
These terminals provide up to 2A of current at 12V
DC
(with
standby battery; 700 mA continuous) for powering bells,
sirens, strobes or other warning type equipment. Connect
the positive side of any alarm warning device to BELL+, the
negative side to BELL–. The BELL output is protected; if too
much current is drawn from these terminals (wiring short)
the BELL PTC will open.
The Bell output is supervised. If no alarm warning device is
being used connect a 1K
Ω
resistor across BELL+ and
BELL– to prevent the panel from displaying a Bell Trouble
condition.
NOTE:
The Bell output is current limited with a 2A PTC.
NOTE:
Steady, Pulsed and Temporal Three Pattern alarms
are supported.
Section 2: Installation and Wiring