55
PC1616/PC1832/PC1864 Installer Programming Quick Reference Chart SIA False Alarm Reduction
SIA Feature
Programming Section
Comments
Range/Default
Requirement
Exit Time
[005], 3rd entry
Access to Entry and Exit delays for each partition and Bell Time Out for the system
For Full or auto arming:
Range:45- 255 seconds
Default: 60 sec.
Required
(programmable)
Progress Annunciation/
Disable - for Silent Exit
[014], Option 6 ON
Enables audible exit beeps from the keypad for the duration of exit delay
Individual keypads
may be disabled
Default: All Enabled
Allowed
Exit Time Restart
[018], Option 7 ON
Enables the exit delay restart feature
Default: Enabled
Required
Auto Stay Arm on
Unvacated Premises
[001]-[004] Zone type 05, 06
Function Key: Stay Arming. All Stay/Away type zones (05, 06) will be automatically
bypassed
If no exit after full arm
Default: Enabled
Required
Exit Time and Progress
Annunciation/Disable
or Remote Arming
[005] and [014] bit 6
System Times and Audible Exit beeps can be disabled when using the Key fob to
arm away the system
Default: Enabled
Allowed
Entry delay(s)
[005], 1st and 2nd entry
Access to Entry and Exit delays for each partition and Bell Time Out for the system
Note: Combined Entry delay and Communications Delay (Abort Window) shall not
exceed 60s
Range: 30 sec. to 4 min.
Default: 30 sees
Required
(programmable)
Abort Window
for Non-Fire zones
[101]-[164] bit 7 ON
Access to zone attributes, i.e, swinger shutdown, transmission delay and cross zone.
Individual zones attribute bit 7 (Transmission delay) is by default ON
May be disabled
by zone or zone type
Default: Enabled
Required
Abort Window - for
Non-Fire zones
[377], 4th entry
Access to the programmable delay before communicating alarms
Note: Combined Entry delay and Communications Delay (Abort Window) shall not
exceed 60s
Range: 15 - 45 sec.
Default: 30 sees
Required
(programmable)
Abort Annunciation
[382], Option 3 ON
Enables the “Communication Cancelled" message display on all keypads
Annunciate that no
alarm was transmitted
Default: Enabled
Required
Cancel Annunciation
[328], 8th entry
Access to the reporting code for Alarm Cancelled
Annunciate that a
Cancel was transmitted
Default: Enabled
Required
Duress Feature
[*][5] Master Code
33rd and 34th entries
Do not derive code from an existing Master/User code (e.g., Master code is 1234,
the duress code should not be 1233 or 1235)
No 1+ derivative of another
user code. No duplicates with
other user codes
Default: disabled
Allowed
Cross Zoning
[018] Option 6
[101]-[164] bit 9 OFF
This option enables Cross Zoning for entire system. Individual zones can be enabled
for Cross zoning via Zone attribute bit 9 in sections [101] - [164]
Programming required
Default: Disabled
Required
Cross Zone Timer
[176]
Access to the programmable Cross Zone timer
May program
Range: 001-255 sec./min.
Default: 60 secs
Allowed
Swinger Shutdown for
Alarms
[377] 1st entry
Access to the swinger shutdown limit for zone alarms
For all non-fire zones
shut down at 1 or 2 trips
Default: 1 Trip
Required
(programmable)
Swinger Shutdown Disable
[101] - [164] bit 6 ON
Access to zone attributes, i.e., swinger shutdown, transmission delay and cross
zone. Individual zones attribute bit 6 (Swinger shutdown enabled) is by default ON
For non-police
response zones
Default: Enabled
Allowed
Fire Alarm Verification
Zone type [29]
Auto Verified Fire, use only with 4 wire type detectors that can be reset by the panel
4-wire smoke detector powered from AUX = and PGM1 - PGM4 (type 03, Sensor
reset)
70 seconds reset and
confirmation time
Default: disabled
Required
Call Waiting Cancel Dial
String
[304], [382], Option 4 OFF
Access to the dialing sequence used to disable call waiting
Dependant on user phone line
Default: disabled
Required
Testing
System Test:
[*][6] Master Code, Option 4
The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on.
Refer to the User Manual (part no. 29007165).
Installer Walk Test Mode:
[901
This mode is used to test each zone on the system for proper functionality.
Alarm Communications
During Walk Test
[382] Option 2:
Enables Communication of zone alarms while installer Walk Test is active.
Walk Test End and Begin
Reporting Codes
[348], 1
st
and 2
nd
Entries
Access to the reporting codes for Walk Test Begin and Walk Test End.